11. TROUBLESHOOTING
11.3
Error Code List
11.3.1
Error codes
Error
Error Message
Code
(D9008)
"INSTRCT.
10
CODE ERR"
"PARAMETER
11
ERROR"
"MISSING END
12
INS."
If an error occurs in the RUN mode, an error display or error code (including a step
number) is stored in the special register by the self-diagnosis function. The error
code reading procedure and the causes of and corrective actions for errors are
shown in Table 11.1.
The followings are the explanation about the descriptions and the causes of the
error messages, error codes and the detailed error codes, and their corrective
actions.
The detailed error codes are stored in D9092 only when using the dedicated
instruction for CC-Link.
Table 11.1 Error codes
Detailed
Error
CPU
Code
States
(D9092)
Stop
Instruction code, which cannot be
decoded by CPU module, is included
in the program.
(1)
(2)
101
Instruction code, which cannot be
decoded by CPU module, is included
in the program.
(1)
(2)
103
Device specified by a dedicated
instruction for CC-Link is not correct.
104
A dedicated instruction for CC-Link
has incorrect program structure.
105
A dedicated instruction for CC-Link
has incorrect command name.
Stop
The contents of parameters of CPU
memory have changed due to noise
or the improper loading of memory.
There is no END ( FEND )
Stop
instruction in the program.
Error and Cause
Memory cassette including
instruction code, which cannot
be decoded, has been loaded.
Since the memory contents have
changed for some reason,
instruction code, which cannot
be decoded, has been included.
Memory cassette including
instruction code, which cannot
be decoded, has been loaded.
Since the memory contents have
changed for some reason,
instruction code, which cannot
be decoded, has been included.
11 - 10
MELSEC-A
Corrective Action
(1) Read the error step by use of
peripheral equipment and correct
the program at that step.
(2) In the case of memory cassette,
rewrite the contents or replace
the cassette with a memory
cassette which stores correct
contents.
(1) Read the error step by use of
peripheral equipment and correct
the program at that step.
(2) In the case of memory cassette,
rewrite the contents or replace
the cassette with a memory
cassette which stores correct
contents.
Read the error step using a peripheral
device and correct the program of the
step.
(1) Load the memory cassette
correctly.
(2) Read the parameter contents of
CPU memory, check and correct
the contents, and write them to
CPU again.
Write END instruction at the end of
program.