Global Protection Parameter Of The Demand Management - Eaton EMR-5000 Installation, Operation And Maintenance Manual

Motor relay
Table of Contents

Advertisement

Global Protection Parameter of the Demand Management

Parameter
Description
Function
Permanent activation or deactivation of module/element. Inactive,
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Alarm
Alarm
Threshold
Threshold (to be entered as primary value)
t-Delay
Tripping Delay
Alarm
Alarm
Threshold
Threshold (to be entered as primary value)
t-Delay
Tripping Delay
Alarm
Alarm
EMR-5000
Setting range
Active
1..n, Assignment
List
Inactive,
Active
1 - 40000000kW
0 - 60min
Inactive,
Active
1 - 40000000kVAr
0 - 60min
Inactive,
Active
www.eaton.com
IM02602012E
Default
Menu path
Inactive
[SysA
/General Settings]
-.-
[SysA
/General Settings]
Inactive
[SysA
/Power
/Watt]
10000kW
[SysA
/Power
/Watt]
0min
[SysA
/Power
/Watt]
Inactive
[SysA
/Power
/VAr]
10000kVAr
[SysA
/Power
/VAr]
0min
[SysA
/Power
/VAr]
Inactive
[SysA
/Power
/VA]
230