RO-4 X Settings

RO-4 X5
Direct Commands of RO-4 X
Parameter
Description
DISARMED
This is the second step, after the "DISARMED Ctrl" has
been activated, that is required to DISARM the relay
outputs. This will DISARM those relay outputs that are
currently not latched and that are not timing out.
CAUTION! RELAYS DISARMED in order to safely
perform maintenance while eliminating the risk of taking
an entire process off-line. (Note: Zone Interlocking and
Supervision Contact cannot be disarmed). YOU MUST
ENSURE that the relays are ARMED AGAIN after
maintenance.
Only available if: DISARMED Ctrl = Active
Force all Outs
By means of this function the normal Relay Output State
can be overwritten (forced). The relay can be set from
normal operation (relay works according to the assigned
signals) to "force energized" or "force de-energized"
state. Forcing all relay outputs of an entire assembly
group has precedence to forcing a single relay output.
Force RO1
By means of this function the normal Relay Output State
can be overwritten (forced). The relay can be set from
normal operation (relay works according to the assigned
signals) to "force energized" or "force de-energized"
state.
Force RO2
By means of this function the normal Relay Output State
can be overwritten (forced). The relay can be set from
normal operation (relay works according to the assigned
signals) to "force energized" or "force de-energized"
state.
Force RO3
By means of this function the normal Relay Output State
can be overwritten (forced). The relay can be set from
normal operation (relay works according to the assigned
signals) to "force energized" or "force de-energized"
state.
EMR-5000
Setting range
Inactive,
Active
Normal,
De-Energized,
Energized
Normal,
De-Energized,
Energized
Normal,
De-Energized,
Energized
Normal,
De-Energized,
Energized
www.eaton.com
IM02602012E
Default
Menu path
Inactive
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/DISARMED
/RO-4 X5]
Normal
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Force RO
/RO-4 X5]
Normal
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Force RO
/RO-4 X5]
Normal
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Force RO
/RO-4 X5]
Normal
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Force RO
/RO-4 X5]