Quick Start Wizard Via Ams Device Manager - Siemens SITRANS LR560 Operating Instructions Manual

Radar transmitters
Hide thumbs Also See for SITRANS LR560:
Table of Contents

Advertisement

Quick Start Wizard via AMS Device Manager

Notes:
• The layout of the dialog boxes shown may vary according to the resolution setting
for your computer monitor
• At each step, you can accept the default values without modification and click on the
next step to proceed.
• After modifying parameters click on Apply inside the Quick Start window to write the
new values to the device.
• Click on OK only if you wish to update all parameters to the device and close AMS.
A Wizard provides an easy step-by-step Quick Start procedure that configures the device for
a simple application.
Quick Start
Step 1 – Identification
1)
Navigate to Configure/Setup > Wizard > Quick Start.
2)
Click on Step 1.
3)
You can accept the default values without modification. (Descriptor, Message, and
Date fields can be left blank.) If desired, make changes then click on Apply.
Step 2 – Application Type
Notes:
• Selecting either STEEL or CONCRETE does a functional reset. (See Master Reset
(4.2.) on page 110.
• Selecting STEEL changes the setting for Position Detect (2.7.3.3.) to Rising Edge. and
for Algorithm (2.7.3.1.) to F.
• Selecting CONCRETE changes the setting for Position Detect (2.7.3.3.) to Rising Edge
and for Algorithm (2.7.3.1.) to ALF.
1)
Click on Step 2.
2)
Select the application type (Steel or Concrete) and the operation (Level, Space, or
1)
Distance
) .