Trend; Peak Values; Electronics Temperature - Siemens SITRANS LR560 Operating Instructions Manual

Radar transmitters
Hide thumbs Also See for SITRANS LR560:
Table of Contents

Advertisement

3.3. Trend

Shows current trend. Samples are saved every minute up to 3200 samples. Once the
maximum number is reached, saved data is overwritten from the beginning.

3.4. Peak Values

To view via SIMATIC PDM:
Open the menu View – Status, and click on the tab Device Status. For more details
Device Status
see
3.4.1. Min. Measured Value
The minimum recorded Sensor value, reported in units defined in Units (2.2.1.).
3.4.2. Max. Measured Value
The maximum recorded Sensor value, reported in units defined in Units (2.2.1.).
3.4.3. Minimum PV
The minimum recorded Primary Value from the Analog Input Function Block 1.
3.4.4. Maximum PV
The maximum recorded Primary Value from the Analog Input Function Block 1.
3.4.5. Minimum SV
The minimum recorded Secondary Value from the Analog Input Function
Block 1.
3.4.6. Maximum SV
The maximum recorded Secondary Value from the Analog Input Function
Block 1.

3.5. Electronics Temperature

3.5.1. Min value
Note: Read only in PDM or AMS. Can be written via the handheld
programmer.
Displays (in degrees C) the minimum temperature recorded by the internal
electronics. The high and low values are maintained over a power cycle.
Via SIMATIC PDM navigate to Maintenance and Diagnostics > Electronics
Temperature.
3.5.2. Max value
Note: Read only in PDM or AMS. Can be written via the handheld
programmer.
Displays (in degrees C) the maximum temperature recorded by the internal
electronics. The high and low values are maintained over a power cycle.
Via SIMATIC PDM navigate to Maintenance and Diagnostics > Electronics
Temperature.
Page 104
SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS
on page 58.
A5E34647946

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents