Siemens SITRANS LR560 Operating Instructions Manual page 44

Radar transmitters
Hide thumbs Also See for SITRANS LR560:
Table of Contents

Advertisement

b.
Press RIGHT arrow
and open the Quick Start Wizard.
c.
At each step, press DOWN arrow
values and move directly to the next item,
or RIGHT arrow
selection is highlighted.
d.
Scroll to desired item and press RIGHT arrow
DOWN arrow
e.
At any time, you can press UP arrow
and return to Measurement mode.
Vessel
Select vessel construction material.
Selecting either STEEL or CONCRETE
does a functional reset (see Master
Reset (4.2.) on page 110).
Selecting STEEL changes the setting
for Position Detect (2.7.3.3.) to Rising
Edge and for Algorithm (2.7.3.1.) to F.
Selecting CONCRETE changes the setting for Position Detect (2.7.3.3.) to Rising Edge
and for Algorithm (2.7.3.1.) to ALF.
Options
Response Rate
Sets the reaction speed of the device to
measurement changes in the target range.
Response
Rate
SLOW
MED
FAST
a)
It may be necessary to reduce this further for FAST applications
Use a setting just faster than the maximum vessel filling or vessel emptying rate (whichever
is greater).
Page 38
SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS
twice to navigate to menu item 1. 1
to open Edit mode: the current
to continue.
*
STEEL
CONCRETE
Vessel Fill Rate/Min or
Empty Rate/Min
0.1 m/min (0.32 ft/min)
*
1.0 m/min (3.28 ft/min)
10.0 m/min (32.8 ft/min)
to accept default
to store the change, then press
to go back, or LEFT arrow
Parameter View
Affected parameters
Damping Filter
600 s
60 s
0 s
to cancel
Edit mode
Average Amount
0.9
0.75
a)
0.75
A5E34647946

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents