4.8.7. Maintenance Status
Indicates which level of maintenance reminder is active.
In SIMATIC PDM, open the menu View – Device Status, click on the
Maintenance tab and check the Calibration Schedule Status window.
4.8.8. Acknowledge Status
Indicates which level of maintenance reminder has been acknowledged.
In SIMATIC PDM, open the menu View – Device Status, click on the
Maintenance tab and check the Calibration Schedule Status window.
4.8.9. Acknowledge
Acknowledges the current maintenance reminder.
To acknowledge a reminder via SIMATIC PDM:
a) Open the menu View – Device Status and click on the Maintenance tab.
b) In the Calibration Schedule Status section click on Acknowledge
Warnings.
To acknowledge a reminder via the the local control buttons or handheld
programmer:
a) Press RIGHT arrow twice to open parameter view and activate Edit Mode.
b) Press RIGHT arrow to acknowledge the reminder.

4.9. Stored Software Version

Displays the version string of the firmware previously uploaded to the LDI (if any).

5. Communication

Note: Default settings in the parameter tables are indicated with an asterisk (*)
unless explicitly stated.

5.1. Device Address

Sets the device address or poll ID on a HART network. For point-to-point
configurations, the standard address is 0. For multidrop configurations, use a non-
zero HART address.
Values
a)
Range should be limited to 0 to 15 for a HART 5 master.
To place the LR560 into HART multidrop:
Set the mA Output Mode (2.6.6.) to Fixed.
Set the Device Address to a non-zero value.
Note: For HART 5 devices, this was a one step process. With HART 6 and above,
this is a two step process.
Page 116
SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS
a)
Range:
0 to 63
Default: 0
A5E34647946