2531 value of the inlet temperature
2532 value of the outlet temperature
2533 state of the flow switch contact
2541 state of configuration
2542 states of management
2543 circuit 1, value of the condensing temperature
2544 circuit 2, value of the condensing temperature
2545 condensing temperature set point
2546 opening percentage calculated for the valve
2611 state of configuration
2612 states of management
2613 value of the evaporating temperature
2614 value of the suction temperature
2615 set point of superheat
2616 value of superheat
2617 opening percentage calculated for the valve
2621 value of the condensing temperature
2622 value of the liquid temperature
2623 value of subcooling
2631 state of configuration
2632 states of management
2633 value of the evaporating temperature
2634 value of the suction temperature
2635 set point of superheat
2636 value of superheat
2637 opening percentage calculated for the valve
2641 value of the condensing temperature
2642 value of the liquid temperature
2643 value of subcooling
2711 state of configuration
2712 states of management
2713 burner 1, state of the safety contact
2714 burner 1, state of the relay
2715 state of the full power relay
2716 burner 2, state of the safety contact
2717 burner 2, state of the relay
2718 opening percentage calculated for the valve
2721 state of configuration
2722 states of management
2723 state of the auxiliary contact
2724 1st stage, state of the relay
2725 2nd stage, state of the relay
2726 power percentage calculated for the triac
2727 power percentage send to the triac
2731 state of configuration
2732 states of management
2733 state of the safety freeze contact
2734 opening percentage calculated for the valve
CLIMATIC RT_UNITARY‐IOM‐1508‐E
Description
4th digit
3rd digit
2nd digit
User
Condenser
Loop
User
Condenser
Valve
User
Expansion Valve
SuperHeat C1
User
Expansion Valve
SubCooling C1
User
Expansion Valve
SuperHeat C2
User
Expansion Valve
SubCooling C2
User
Heater
Gas
User
Heater
Electrical
User
Heater
Hot Water
1st digit
R/W/Z Min
Std
Inlet
R
‐99,9
Outlet
R
‐99,9
Flow iD
R
0
Config.
R
0
Status
R
23
23
Cond. 1
R
‐99,9
Cond. 2
R
‐99,9
Setting
R
25
30
Opening
R
0
Config.
R
0
Status
R
23
23
Evap.
R
‐99,9
Suction
R
‐99,9
Setting
R
‐72
S.Heat
R
‐99,9
Opening
R
0
Cond.
R
‐99,9
Liquid
R
‐99,9
S.Cool
R
‐99,9
Config.
R
0
Status
R
23
23
Evap.
R
‐99,9
Suction
R
‐99,9
Setting
R
‐72
S.Heat
R
‐99,9
Opening
R
0
Cond.
R
‐99,9
Liquid
R
‐99,9
S.Cool
R
‐99,9
Config.
R
0
Status
R
23
23
Sta.1 iD
R
0
Relay 1
R
0
High Pow.
R
0
Sta.2 iD
R
0
Relay 2
R
0
Modul.
R
0
Config.
R
0
Status
R
23
23
State iD
R
0
Relay 1
R
0
Relay 2
R
0
Modul.
R
0
Output
R
0
Config.
R
0
Status
R
23
23
Freeze iD
R
0
Modul.
R
0
Max
0
99,9
0
99,9
0
1
0
21
62
0
99,9
0
99,9
45
0
100
0
21
62
0
99,9
0
99,9
7
324
0
99,9
0
100
0
99,9
0
99,9
0
99,9
0
21
62
0
99,9
0
99,9
7
324
0
99,9
0
100
0
99,9
0
99,9
0
99,9
0
21
62
0
1
0
1
0
1
0
1
0
1
0
100
0
21
62
0
1
0
1
0
1
0
100
0
100
0
21
62
0
1
0
100
. 86 .