Lennox CLIMATIC series User Manual page 73

Baltic, flexy, flexair, energy, aircoolair, compactair, flatair, aqualean
Table of Contents

Advertisement

BMS
NV_Name
DESCRIPTION
alarm, 7
bit.0 = (341) circuit 3, high pressure, faulty sensor
bit.1 = (342) circuit 3, low presure, faulty sensor
bit.2 = (343) circuit 3, liquid temperature, faulty probe
bit.3 = (344) circuit 3, suction temperature, faulty probe
bit.4 = (314) circuit 3, compressor, electrical failure
bit.5 = (315) circuit 3, high pressure cut off
bit.6 = (316) circuit 3, reversing valve, blocked
nvo_Error_Bits_6
bit.7 = (317) circuit 3, low pressure cut off
bit.8 = (319) circuit 3, low condensing temperature
bit.9 = (329) circuit 3, high condensing temperature
bit.10 = (328) circuit 3, lop low operating pressure
bit.11 = (327) circuit 3, mop, maximum operating pressure
bit.12 = (321) circuit 3, low superheat
bit.13 = (322) circuit 3, high superheat
bit.14 = (323) circuit 3, low subcooling
bit.15 = (324) circuit 3, high subcooling
digital, 1
bit.0 = unit, general on/off, start & stop, set point
bit.1 = unit, reset alarms, set point
bit.2 = bms, night mode forced by bms
bit.3 = blower, bms day, setpoint for activation operation, in room control dead
zone
bit.4 =
bit.5 =
bit.6 =
nvi_Bool_Bits_1
bit.7 =
nvo_Bool_Bits_1
bit.8 =
bit.9 =
bit.10 = remote control, activation of bm j14 no7
bit.11 = remote control, activation of bm j15 no12
bit.12 = remote control, activation of be-1 j5 no1
bit.13 = remote control, activation of be-1 j6 no2
bit.14 = remote control, activation of be-1 j7 no3
bit.15 = remote control, activation of be-1 j8 no4
CLIMATIC RT_UNITARY-IOM-1508-E
MIN
FACT.
MAX
0
~
65536
0
0
0
1
~
~
~
0
~
65536
~
~
0
0
0
0
0
0
• 71 •