Lennox CLIMATIC series User Manual page 86

Baltic, flexy, flexair, energy, aircoolair, compactair, flatair, aqualean
Table of Contents

Advertisement

Menu
2271 set point of dehumidification
2272 set point of humidification
2281 activation of tcb feature
2282 state of 'g' signal
2283 state of 'b' signal
2284 state of 'y1' signal
2285 state of 'y2' signal
2286 state of 'w1' signal
2287 state of 'w2' signal
2311 state of configuration
2312 states of management
2313 state of the auxiliary contact
2314 state of the relay
2315 count value of operating time
2316 setpoint for activation operation of component
2317 setpoint for activation operation in room control dead zone
2318 temperature threshold for activation night refreshment function
2321 state of configuration
2322 states of management
2323 state of the safety contact of inverter
2324 speed percentage calculated for the inverter
2325 speed percentage send to the inverter
2326 calculated value of air flow or evaporator flow switch
2327 choice of speed function
2328 nominal threshold for air flow control
2329 low threshold for air flow control
2331 state of configuration
2332 value of differential pressure sensor on air flow
2333 air flow threshold alarm
2334 filters missing threshold alarm
2335 dirty filters threshold alarm
2341 state of smoke detection contact
2411 state of configuration
2412 value of the evaporating pressure or temperature
2413 value of the suction temperature
2414 value of the condensing pressure or temperature
2415 value of the liquid temperature
2416 low pressure, state of the safety
2417 state of the reversing valve
2418 speed percentage calculated for the inverter
2419 speed percentage send to the inverter
2421 state of configuration
2422 states of management
2423 state of the auxiliary contact
2424 state of the relay
2425 count value of operating time
CLIMATIC RT_UNITARY‐IOM‐1508‐E
Description
4th digit
3rd digit
2nd digit
User
Control
Humidity Sp
User
Control
Tcb
User
Blower
Fan
User
Blower
Speed
User
Blower
Air Flow
User
Blower
Safety
User
Compressor
Circuit 1
User
Compressor
Circ.1 Comp.1
1st digit
R/W/Z Min
Std
Sp. Deh.
R/W/Z
0
10
Sp. Hum.
R/W/Z
0
Mode
R/W
0
‐ G
R
0
‐ B
R
0
‐ Y1
R
0
‐ Y2
R
0
‐ W1
R
0
‐ W2
R
0
Config.
R
0
Status
R
23
23
State iD
R
0
Relay
R
0
Run Time
R
0
Enabled
R/W/Z
0
Dead Z.
R/W/Z
0
Night Eco
R/W
8
22
Config.
R
0
Status
R
23
23
State iD
R
0
Inverter
R
0
Output
R
0
Flow
R
0
Function
R/W
0
Flow H.
R/W
0
85
Flow L.
R/W
0
33
Config.
R
0
Delta dP
R
0
Air Flow
R/W
0
25
Missing
R/W
0
50
Dirty
R/W
50
250
Fire iD
R
0
Config.
R
0
Evap.
R
‐1
‐1
Suction
R
‐99,9
Cond.
R
‐1
‐1
Liquid
R
‐99,9
Low P.
R
0
R.Valve
R
0
Inverter
R
0
Output
R
0
Config.
R
0
Status
R
23
23
State iD
R
0
Relay
R
0
Run Time
R
0
Max
100
0
100
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
21
62
0
1
0
1
0
9999
1
1
1
1
35
0
21
62
0
1
0
100
0
24000
0
24000
0
2
100
100
0
21
0
1000
1000
1000
1000
0
1
0
21
20
0
99,9
45
0
99,9
0
1
0
1
0
100
0
1
0
21
62
0
1
0
1
0
9999
. 84 .