Lennox CLIMATIC series User Manual page 63

Baltic, flexy, flexair, energy, aircoolair, compactair, flatair, aqualean
Table of Contents

Advertisement

BMS
@Address
50
Analog
51
Analog
52
Analog
53
Analog
54
Analog
55
Analog
56
Analog
57
Analog
58
Analog
59
Analog
60
Integer
61
Integer
62
Integer
63
Integer
64
Integer
65
Integer
66
Integer
67
Integer
68
Integer
69
Integer
70
Integer
71
Integer
72
Integer
73
74
Integer
CLIMATIC RT_UNITARY-IOM-1508-E
R/W
DESCRIPTION
hot water coil, opening percentage calculated for the valve
R
humidifi er, power percentage calculated for the proportional signal
R
remote control, value of the signal, be-1 b1, temperature
R
R
remote control, value of the signal, be-1 b2, temperature
remote control, value of the signal, be-1 b3, temperature
R
remote control, value of the signal, be-1 b4, temperature
R
R
remote control, value of the signal, be-1 b1, humidity
R
remote control, value of the signal, be-1 b2, humidity
remote control, value of the signal, be-1 b3, humidity
R
R
remote control, value of the signal, be-1 b4, humidity
R
unit, count value (weight low) of operating time
unit, count value (weight high) of operating time
R
R
blower, count value (weight low) of operating time
R
blower, count value (weight high) of operating time
R
circuit 1 compressor 1, count value (weight low) of operating time
circuit 1 compressor 1, count value (weight high) of operating time
R
R
circuit 1 compressor 2, count value (weight low) of operating time
R
circuit 1 compressor 2, count value (weight high) of operating time
R
circuit 2 compressor 1, count value (weight low) of operating time
R
circuit 2 compressor 1, count value (weight high) of operating time
R
circuit 2 compressor 2, count value (weight low) of operating time
R
circuit 2 compressor 2, count value (weight high) of operating time
R
blower, calculated value of air fl ow
not used
Alarm, 1
bit.0 = (70) Real Time Clock
bit.1 = (71) BE.1, Communication Bus
bit.2 = (72) BE.2, Communication Bus
bit.3 = (9) Unit power supply
bit.4 = (81) Room Temperature, Probe
bit.5 = (82) Room Humidity, Sensor
bit.6 = (83) Outside Temperature, Probe
R
bit.7 = (85) Supply Temperature, Probe
bit.8 = (88) Return Temperature, Probe
bit.9 = (22) Supply Temperature, Too Low
bit.10 = (80) Air Flow, Sensor
bit.11 = (73) Blower, Inverter, Communication Bus
bit.12 = (1) Blower, Flow Switch Cut Off
bit.13 = (91) Blower, Fan
bit.14 = (92) Blower, Inverter
bit.15 = (99) Fire / Smoke, Detected
MIN
Fact.
MAX
0.0
~
100.0
0.0
~
100.0
-99.9
~
99.9
-99.9
~
99.9
-99.9
~
99.9
-99.9
~
99.9
0.0
~
100.0
0.0
~
100.0
0.0
~
100.0
0.0
~
100.0
0
~
65536
0
~
65536
0
~
65536
0
~
65536
0
~
65536
0
~
65536
0
~
65536
0
~
65536
0
~
65536
0
~
65536
0
~
65536
0
~
65536
0
~
32767
-32768
~
32767
0
~
65536
• 61 •