INPUTS / OUTPUTS CLIMATIC BOARDS
APPENDIX 5
Analogic inputs - CLIMATIC 60
BM:J3.B1 (NTC)
BM:J3.B2 (NTC)
BM:J3.B3 (NTC)
BM:J3.B4 (NTC)
BM:J3.B5 (NTC, 4-20)
BM:J3.B6 (NTC, 0-5)
BM:J3.B7 (NTC, 0-5)
BM:J18.B8 (NTC)
BM:J18.B9 (NTC)
BM:J18.B10 (NTC, 4-20)
BM:J18.B11 (NTC, 0-5)
BM:J18.B12 (NTC, 0-5)
DC Modbus
Hr Modbus
Hr Modbus
BE.1:J9.B1
BE.1:J9.B2
BE.1:J10.B3
BE.1:J10.B4
BE.2:J9.B1
BE.2:J9.B2
BE.2:J10.B3
BE.2:J10.B4
• 76 •
Small
Return or Room (NTC)
Circuit 1, Condensing -1~45b (4~20mA)
Circuit 1, Evaporating -1~20b (0~5V)
Filters/Fan 0~500 Pa (0~5V) or Room (NTC)
X
X
X
X
X
[CO2S] Indoor, Air Quality CO
[ADCP] Outside, Humidity (4~20mA) or [DCBO] Remote control: Custom
[RLKD] Circuit 1, Liquid (NTC) or Water Condenser, Inlet (NTC) or [DCBO] Remote control :
Water Condenser, Outlet (NTC) or [DCBO] Remote control : Custom
Wheel Recovery, Pressure (0~5V)
Outside (NTC)
Supply (NTC)
Circuit 1, Suction (NTC)
[RLKD] Circuit 2, Liquid (NTC)
Circuit 2, Suction (NTC)
Circuit 2, Condensing -1~45b (4~20mA)
Circuit 2, Evaporating -1~120b (0~5V)
[DC] Room, Temperature
[ADCP] Room, Temperature
[ADCP] Room, Humidity
(4~20mA) or [DCBO] Remote control: Custom
2
Custom
Outside (NTC)
CLIMATIC RT_UNITARY-IOM-1508-E
Medium
Return (NTC)
Room (NTC)