2191 value of the signal, be‐1 b1
2192 value of the signal, be‐1 b2
2193 value of the signal, be‐1 b3
2194 value of the signal, be‐1 b4
2211 value of the outside temperature
2212 Origin of the Value (BM, BE, BUS, Mast/Slav or BMS)
2213 value of the room temperature
2214 Origin of the Value (BM, BE, BUS, Mast/Slav or BMS)
2215 value of the supply temperature
2216 value of the return temperature
2221 value of the room temperature
2222 customer (dc/dm) set point
2223 set value of cooling mode
2224 set value of heating mode
2225 states of cooling mode
2226 states of heating mode
2227 power factor of cooling mode
2228 power factor of heating mode
2231 value of the supply temperature
2232 Blowing air temperature set point
2233 activation of the smoothing function of temperature
2234 count value of cooling operating time
2235 count value of heating operating time
2241 Dynamic set point (cooling setpoint offset according to outside temperature)
2242 set point of cooling mode
2243 set point of heating mode
2244 outdoor temperature low threshold for room temperature setpoint slope
2245 room temp setpoint offset according to low outdoor air temp
2246 outdoor temperature high threshold for slope on the room temperature setpoint
2247 room temp setpoint offset according to high outdoor air temp
2248 room temperature threshold for unloading cooling mode
2249 room temperature threshold for unloading heating mode
2251 low limit threshold in cooling mode
2252 high limit threshold in heating mode
2253 offset for high limit threshold in cooling mode
2254 offset for low limit threshold in heating mode
2255 outdoor temperature low threshold for slope on the supply temperature setpoint
2256 coefficient of the low outside temperature for the slope of the supply temperature setpoint
2257 outdoor temperature high threshold for slope on the supply temperature setpoint
2258 coefficient of the high outside temperature for the slope of the supply temperature setpoint
2261 value of the outside humidity
2262 calculated value of the outside absolute humidity
2263 from the value
2264 value of the room humidity
2265 calculated value of the room absolute humidity
2266 from the value
2267 power factor of dehumidification function
2268 power factor of humidification
2269 state of enthalpy control
CLIMATIC RT_UNITARY‐IOM‐1508‐E
Description
4th digit
3rd digit
2nd digit
User
Unit
Cust. Signal
User
Control
Temperature
User
Control
Room
User
Control
Supply
User
Control
Room Sp
User
Control
Supply Sp
User
Control
Humidity
1st digit
R/W/Z Min
Std
Be.1‐B1
R
‐5
Be.1‐B2
R
‐5
Be.1‐B3
R
‐5
Be.1‐B4
R
‐5
Outside
R
‐99,9
 From
R
23
23
Room
R
‐99,9
 From
R
23
23
Supply
R
‐99,9
Return
R
‐99,9
Temp.
R
‐99,9
Sp Cust.
R/W
8
20,5
Set Cool.
R
8
19
Set Heat.
R
8
22
State.C
R
23
23
State.H
R
23
23
Pf.Cool.
R
0
Pf.Heat.
R
0
Temp.
R
‐99,9
Setting
R
1
20,5
Smooth
R/Z
0
Time.Cool
R
0
Time.Heat
R
0
Sp.Dyna.
R/W/Z
0
20
Sp.Cool.
R/W/Z
8
19
Sp.Heat.
R/W/Z
8
22
Out.Low
R/W
‐20
Coef.Low
R/W
‐50
Out.High
R/W
‐20
30
Coef.High
R/W
‐50
Limit C.
R/W
0
Limit H.
R/W
0
40
Lim.Cool
R/W
4
12
Lim.Heat
R/W
4
38
Adj.Cool
R/W
‐5
Adj.Heat
R/W
‐5
Out.Low
R/W
‐20
Coef.Low
R/W
‐50
Out.High
R/W
‐20
30
Coef.High
R/W
‐50
Outside
R
0
 Absol.
R
0
 From
R
23
23
Room
R
0
 Absol.
R
0
 From
R
23
23
Pf.Deh.
R
0
Pf.Hum.
R
0
Enthalpy
R
0
Max
0
5
0
5
0
5
0
5
0
99,9
62
0
99,9
62
0
99,9
0
99,9
0
99,9
35
35
35
62
62
0
100
0
100
0
99,9
70
0
1
0
9999
0
9999
20
35
35
0
50
0
50
50
0
50
0
40
40
38
38
0
5
0
5
0
50
0
50
50
0
50
0
100
0
99,9
62
0
100
0
99,9
62
0
100
0
100
0
1
. 83 .