ABB FSM4000 Operating Instruction page 69

Electromagnetic flowmeter
Hide thumbs Also See for FSM4000:
Table of Contents

Advertisement

Submenu/parameter
Adj. empty pipe
1000
Adj. full pipe
500
Threshold
100000
Alarm. e. pipe
Off
Iout at e. pipe
Low Alarm
Submenu
Display
Display mode
1 big, 1 small
D184B140U02
Value range
Comment
Adjustment value for empty meter pipe. The pipeline must
Manual
be empty. After the adjustment is completed, the
Autom. Adjust
transmitter displays the adjustment value and calculates a
new threshold value.
Not displayed, if DEP is switched off or DEP mode is
standard.
Adjustment value for full meter pipe. The pipeline must be
Manual
filled. After the adjustment is completed, the transmitter
Autom. Adjust
displays the adjustment value and calculates a new
threshold value.
Not displayed, if DEP is switched off or DEP mode is
standard.
Numeric entry
Threshold value for turning off the "Empty pipe" function.
This value is calculated and entered internally after the
adjustment "Empty pipe" or "Full pipe" is completed. It can
also be entered manually (e.g., after both adjustment
values (full and empty) are determined and the threshold,
based on these values, is optimized (the transmitter
always uses only the most recent adjustment value)). The
threshold value is the basic criteria used for the DEP
function. The adjustment values are used only to
calculate the threshold.
Not displayed, if DEP is switched off or DEP mode is
standard.
Off
If the alarm is switched on, the empty pipe contact is
actuated when the pipe empties. The "empty pipe" or
On
"General alarm" functions must be selected in the "Progr.
in/output" submenu. When the function is turned off, the
alarm does not respond.
Not displayed, if DEP is switched off.
Set the current output value to Low or High in event of
Low Alarm
error.
High Alarm
Not displayed, if DEP is switched off.
0%
Select each different line displayed for the process
indicators in this submenu. You can also adapt the
contrast of the display to local conditions by pressing the
arrow keys.
1 big, 1 small,
Select 1 big and 1 small line or 4 small lines.
4 small
FSM4000
Parameterization
69