Submenu/parameter
Anzeige 1. Zeile
TBT → Value
1st line
TBT → Status
1st line
TB VolFlowValue
1st line
TB Total → V Value
1st line
TB Total ← R Value
1st line
TB TotalDiffValue
1st line
TB AI1 Out. Value
1st line
TB AI2 Out. Value
1st line
TB AI3 Out. Value
1st line
PID In. Value
1st line
PID Out. Value
1st line
PID Cas_In. Value
1st line
PID FF_Val.Value
D184B140U02
Value range
Comment
FB TOT1 Total. Displays the total value for the totalizer
block. The displayed unit is UNIT_TOTAL.
FB TOT1 Status. Displays the current mode of the
particular block and the status of the output variables
(Total. Status). The substatus is displayed after the
status, if applicable. Example: BAD 3 means status is
BAD, substatus 3 = device failure.
FB TOT2 Total. Displays the total value for the totalizer
block. The displayed unit is UNIT_TOTAL.
FB TOT2 Status. Displays the current mode of the
particular block and the status of the output variables
(Total. Status). The substatus is displayed after the
status, if applicable. Example: BAD 3 means status is
BAD, substatus 3 = device failure.
For information about the numeric code, refer to the
interface documentation.
For devices with FOUNDATION Fieldbus, the following
options are available: Flowrate in percentage, engineering
unit, in m/s, Bar graph, Totalizer, Totalizer→ F, Totalizer
← R, Totalizer diff., Detector empty pipe; additional
options: FF address, displayed in hexadecimal.
Displays the value or status of the flowrate (TB
Primary_Value, Index 14).
Displays the value or status of the Totalizer →Forward
(TB Secondary_Value, Index 28).
Displays the value or status of the Totalizer ← R (TB
Third_Value, Index 30).
Displays the value or status of the totalizer (TB
Fourth_Value, Index 31).
Displays the value or status of the parameter Out for the
function block AI1.
Displays the value or status of the parameter Out for the
function block AI2.
Displays the value or status of the parameter Out for the
function block AI3.
Displays the value or status of the parameter In for the
function block PID.
Displays the value or status of the parameter Out for the
function block PID.
Displays the value or status of the parameter Cas_In for
the function block PID.
Displays the value or status of the parameter FF_Val for
the function block PID.
FSM4000
Parameterization
71