Hand On/Auto On Mode; Application Selections - Danfoss VLTAutomationDrive FC 360 Quick Manual

Table of Contents

Advertisement

Quick Start

1.2 Hand On/Auto On Mode

1
1
After installation (see 3 Installation) there are two simple
ways to start up the frequency converter, Hand On and
Auto On mode. The first time the frequency converter is
powered up it will be in auto on mode.
On
Warn
Hand
D
Illustration 1.3 Location of Hand On, Off Reset and Auto On keys
on the NLCP
Press [Hand On] to provide a local start command
to the frequency converter. It is then possible to
increase and decrease the speed using the arrow
keys on the LCP.
Press [Off/Reset] to stop the frequency converter.
Press [Auto On] to control the frequency
converter either via control terminals or serial
communication.
CAUTION
Since the frequency converter is in auto on mode at first
power up, the frequency converter may start the motor
directly.
NOTE
Terminal 27 Digital input (5-12) has coast inverse as default
setting. Connect terminal 12 and 27 to test Hand On/Auto
On running.
For LCP operation, see 4 User Interface and Programming.

1.3 Application Selections

Use the selections for quick application set-up of the most
common applications by setting 0-16 Application Selections.
When necessary, the selections can be modified for
individual needs. All selections are for Auto On mode.
NOTE
When an application is selected, relevant parameters are
automatically set. Further setups to all parameters based
on specific requirements is still possible.
4
OK
Alarm
Auto
Reset
On
MG06A102 - VLT
®
VLT
AutomationDrive FC 360 Quick Guide
CAUTION
If any of the applications below are selected, relay 1 will
be set to [Running] and relay 2 will be set to [Alarm]
[1] Process Closed Loop
Application
Pumps, fans, compressors
Description
For applications where a
value (e.g. pressure,
temperature) must be
kept at a desired level by
sensor feedback
On
Parameter settings
1-00 (Configuration Mode): [3] Process Close Loop
1-03 (Torque Characteristics): [1] Variable Torque
3-00 (Ref Range): [0] Min- Max
3-15 (Ref Source 1): [0] No Function
4-12 (Motor Low Limit): 30.0 Hz
4-14 (Motor High Limit): 50.0 Hz
5-10 (DI 18 Selection): [8] Start
5-12 (DI 27 Selection): [2] Coast Inverse
5-14 (DI 32 Selection): [14] Jog
5-40 (Relay 1 Selection): Running
5-40 (Relay 2 Selection): Alarm
6-22 (AI 54 Low): 4.0 mA
6-23 (AI 54 High): 20.0 mA
6-29 (AI 54 Mode): [0] Current Mode
6-70 (Term 45 Mode): [0] 0-20 mA
6-71 (AO45): [100] Output freq
6-90 (Term 42 Mode): [0] 0-20 mA
6-91 (AO42): [103] Motor current
7-20 (Process CL feedback source): [2] Analog input 54
Table 1.2
®
is a registered Danfoss trademark
FC 360
+24V 12
DI1 18
Start
DI2 19
DI3 27
Coast inverse
DI4 29
DI5 32
Jog
DI6 33
DI7 31
COM 20
+10V 50
AI1
53
-
+
4-20
AI2
54
mA
COM 55
AO1 45
AO2 42
1
R1
2
3
4
R2
5
6