Warnings and Alarms
No.
Description
54
AMA small motor
55
AMA parameter range
56
AMA interrupt
57
AMA timeout
58
AMA internal
59
Current limit
61
Encoder loss
63
Mechanical Brake Low
65
Control card temp
66
Heat sink Temperature Low
70
Illegal FC config
79
Undefined
80
Drive Initialised to Default Value
87
Auto DC braking
95
Broken belt
101
Flow/pressure info missing
250
New sparepart
251
New typecode
nw
Not While RUNning
run
Err.
A wrong password was entered
1)
These faults may be caused by mains distortions. Installing Danfoss Line Filter may rectify this problem.
Table 6.1 Warnings and Alarms Code List
®
VLT
AutomationDrive FC 360 Quick Guide
Warning
Alarm
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
®
MG06A102 - VLT
is a registered Danfoss trademark
Trip
Cause of Problem
Lock
The motor is too small for the AMA to operate.
The parameter values of the motor are outside of
the acceptable range. AMA will not run.
The user has interrupted the AMA.
Contact your Danfoss supplier.
VLT overload.
Actual motor current has not exceeded "release
brake" current within "start delay" time window.
X
The cutout temperature of the control card is 80 °C.
The frequency converter is too cold to operate. This
warning is based on the temperature sensor in the
IGBT module.
X
The control card and power card are incompatible.
All parameter settings are initialized to default
settings.
Occurs when copying from LCP if the LCP contains
erroneous data - or if no data was uploaded to the
LCP.
X
X
A component in the frequency converter has been
replaced.
X
The power card or other components have been
replaced and the typecode changed.
Parameter can only be changed when the motor is
stopped.
Occurs when using a wrong password for changing
a password-protected parameter.