Installation

3 Installation

3.1 Mechanical Installation

Select the best possible operation site by considering the
following:
3
3
Ambient operating temperature
Installation method
How to cool the unit
Position of the frequency converter
Cable routing
Power source supplying correct voltage and
necessary current
Motor current rating within the maximum current
from the frequency converter
Correct rating of external fuses and circuit
breakers
Cooling and Mounting:
Top and bottom clearance for air cooling must be
provided, see Table 3.1 for clearance requirements
Derating for temperatures starting from 45°C and
elevation 1000m above sea level must be
considered. See the equipment Design Guide for
detailed information.
Enclosure
Clearance above and below the
unit [mm]
Table 3.1 Minimum Airflow Clearance Requirements
Mount the unit vertically
IP20 units (but NOT IP21 units) allow side by side
installation
Improper mounting can result in over heating
and reduced performance
Use the slotted mounting holes on the unit for
wall mounting, when provided
See 8.4 Connection Tightening Torques for proper
tightening specifications.
10
®
VLT
AutomationDrive FC 360 Quick Guide
J1-J5
J6/J7
100-200
®
MG06A102 - VLT
is a registered Danfoss trademark