Wiring Examples

5 Wiring Examples
The examples in this section are intended as a quick
reference for common functionalities.
FC
+24 V
12
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
5
5
D IN
32
D IN
33
D IN
31
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
Table 5.1 AMA with T27 Connected
FC
+24 V
12
18
D IN
19
D IN
20
COM
27
D IN
29
D IN
32
D IN
33
D IN
D IN
31
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
Table 5.2 Analog Speed Reference (Voltage)
28
®
VLT
AutomationDrive FC 360 Quick Guide
Parameters
Function
Setting
1-29 Automatic
Motor
[1] Enable
Adaptation
complete
(AMA)
AMA
5-12 Terminal 27
[2]* Coast
Digital Input
inverse
* = Default Value
Notes/comments: Parameter
group 1-2* must be set
according to motor
NOTE
If terminal 12 and 27 are
not connected, set 5-12 to
[0]
Parameters
Function
Setting
6-10 Terminal 53
Low Voltage
0.07 V*
6-11 Terminal 53
10 V*
High Voltage
6-14 Terminal 53
0RPM
Low Ref./Feedb.
Value
6-15 Terminal 53
1500 RPM
High Ref./Feedb.
Value
+
6-19 Terminal 53
[1] Voltage
Mode
* = Default Value
-
Notes/comments:
-10 - +10V
MG06A102 - VLT
FC
+24 V
12
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
32
D IN
33
D IN
D IN
31
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
Table 5.3 Analog Speed Reference (Current)
FC
+24 V
12
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
31
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
Table 5.4 Start/Stop with Reversing and 4 Preset Speeds
®
is a registered Danfoss trademark
Parameters
Function
Setting
6-12 Terminal 53
4 mA*
Low Current
6-13 Terminal 53
20 mA*
High Current
6-14 Terminal 53
0 RPM
Low Ref./Feedb.
Value
6-15 Terminal 53
1500 RPM
High Ref./Feedb.
Value
+
6-19 Terminal 53
[0] current
Mode
* = Default Value
-
Notes/comments:
4 - 20mA
Parameters
Function
5-10 Terminal 18
[8] Start
Digital Input
5-11 Terminal 19
[10]
Digital Input
Reversing*
5-12 Terminal 27
[0] No
Digital Input
operation
5-14 Terminal 32
[16] Preset
Digital Input
ref bit 0
5-15 Terminal 33
[17] Preset
Digital Input
ref bit 1
3-10 Preset
Reference
Preset ref. 0
25%
Preset ref. 1
50%
Preset ref. 2
75%
Preset ref. 3
100%
* = Default Value