3.3 Serial Communication

Connect RS-485 serial communication wiring to terminals
(+)68 and (-)69.
Screened serial communication cable is
recommended
See 3.2.2 Earth (Grounding) Requirements for
proper grounding
61
68
69
Illustration 3.11 Serial Communication Wiring Diagram
For basic serial communication set-up, select the following
1.
Protocol type in 8-30 Protocol.
2.
Frequency converter address in 8-31 Address.
3.
Baud rate in 8-32 Baud Rate.
Two communication protocols are internal to the
frequency converter. Follow motor manufacturer
wiring requirements.
Danfoss FC
Modbus RTU
Functions can be programmed remotely using
the protocol software and RS-485 connection or
in parameter group 8-** Communications and
Options
Selecting a specific communication protocol
changes various default parameter settings to
match that protocol's specifications along with
making additional protocol-specific parameters
available
®
VLT
AutomationDrive FC 360 Quick Guide
+
RS-485
®
MG06A102 - VLT
is a registered Danfoss trademark
3
3
17