Module Description; General Technical Specifications; General Technical Specifications (Part 1) - Siemens SIMATIC S5 Manual

Ip 267 stepper motor controller
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

IP 267
3

Module Description

This chapter will give you an overview of the technical specifications of the IP 267,
the power supply, terminal assignments of the terminal block, input and output
signals, status displays on the frontplate and a list of the connecting cables for the
power sections.
3.1

General Technical Specifications

Table 3-1. General Technical Specifications (Part 1)
Climatic Environmental Conditions
Temperature
Operation
- Horizontal arrangement
- Vertical arrangement
Storage/shipping
Temperature change
- Operation
- Storage/shipping
Relative humidity
Atmospheric pressure
- Operation
- Storage/shipping
EWA 4NEB 812 6061-02a
Mechanical Environmental Conditions
Vibration
- tested with
0 to +60° C
0 to+40° C
(Intake air
temperature
measured at the
bottom of the
modules)
-40° C to +70° C
Shock
- tested with
max. 10° C / h
max. 20° C / h
Free-fall
to DIN 40040
- tested with
15 ... 95% (indoor)
Noncondensing
860 to 1060 hPa
660 to 1060 hPa

Module Description

to IEC 68-2-6
10 to 57 Hz,
(constant
amplitude
0.15 mm/0.006 in.
)
57 to500 Hz,
(constant
acceleration 2 g)
to IEC 68-2-27
12 shocks
(semisinusoidal
15 g / 11 ms)
to IEC 68-2-32
Height of fall
1 m/3.3ft.
3-1