APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 29 of 65)
ADDR
REGISTER NAME
617B
September Average Ambient Temperature
617C
October Average Ambient Temperature
617D
November Average Ambient Temperature
617E
December Average Ambient Temperature
Transformer Loss of Life (Read/Write Command)
6180
Transformer Loss of Life Clear Command
Transformer Percent Differential (Read/Write Grouped Setting)
6200
Percent Differential Function
6201
Percent Differential Pickup
6202
Percent Differential Slope 1
6203
Percent Differential Break 1
6204
Percent Differential Break 2
6205
Percent Differential Slope 2
6206
Inrush Inhibit Function
6207
Inrush Inhibit Level
6208
Overexcitation Inhibit Function
6209
Overexcitation Inhibit Level
620A
Percent Differential Block
620B
Percent Differential Target
620C
Percent Differential Events
620D
Transformer Inrush Inhibit Mode
Transformer Instantaneous Differential (Read/Write Grouped Setting)
6220
Transformer Instantaneous Differential Function
6221
Transformer Instantaneous Differential Pickup
6222
Transformer Instantaneous Differential Block
6223
Transformer Instantaneous Differential Target
6224
Transformer Instantaneous Differential Events
Overfrequency (Read/Write Setting) (4 modules)
64D0
Overfrequency 1 Function
64D1
Overfrequency 1 Block
64D2
Overfrequency 1 Source
64D3
Overfrequency 1 Pickup
64D4
Overfrequency 1 Pickup Delay
64D5
Overfrequency 1 Reset Delay
64D6
Overfrequency 1 Target
64D7
Overfrequency 1 Events
64D8
Reserved (4 items)
64DC
...Repeated for Overfrequency 2
64E8
...Repeated for Overfrequency 3
64F4
...Repeated for Overfrequency 4
Power Swing Detect (Read/Write Grouped Setting)
65C0
Power Swing Detect Function
65C1
Power Swing Detect Source
65C2
Power Swing Detect Mode
65C3
Power Swing Detect Supervision
65C4
Power Swing Detect Forward Reach
65C5
Power Swing Detect Forward RCA
65C6
Power Swing Detect Reverse Reach
65C7
Power Swing Detect Reverse RCA
65C8
Power Swing Detect Outer Limit Angle
65C9
Power Swing Detect Middle Limit Angle
65CA
Power Swing Detect Inner Limit Angle
65CB
Power Swing Detect Delay 1 Pickup
65CC
Power Swing Detect Delay 1 Reset
GE Multilin
RANGE
-60 to 60
-60 to 60
-60 to 60
-60 to 60
0 to 1
0 to 1
0.05 to 1
15 to 100
1 to 2
2 to 30
50 to 100
0 to 2
1 to 40
0 to 1
1 to 40
0 to 65535
0 to 2
0 to 1
0 to 2
0 to 1
2 to 30
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 65535
0 to 5
20 to 65
0 to 65.535
0 to 65.535
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 1
0.05 to 30
0.1 to 500
40 to 90
0.1 to 500
40 to 90
40 to 140
40 to 140
40 to 140
0 to 65.535
0 to 65.535
T60 Transformer Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
---
1
F126
---
1
F102
pu
0.001
F001
%
1
F001
pu
0.001
F001
pu
0.001
F001
%
1
F001
---
1
F168
% fo
0.1
F001
---
1
F169
% fo
0.1
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F189
---
1
F102
pu
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
1
F300
---
1
F167
Hz
0.01
F001
s
0.001
F001
s
0.001
F001
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
---
1
F513
pu
0.001
F001
ohms
0.01
F001
degrees
1
F001
ohms
0.01
F001
degrees
1
F001
degrees
1
F001
degrees
1
F001
degrees
1
F001
s
0.001
F001
s
0.001
F001
DEFAULT
20
10
10
-10
B
0 (No)
0 (Disabled)
100
25
2000
8000
100
1 (Adapt. 2nd)
200
0 (Disabled)
100
0
0 (Self-reset)
0 (Disabled)
0 (Per phase)
0 (Disabled)
8000
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0
0 (SRC 1)
6050
500
500
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
0 (Two Step)
600
5000
75
5000
75
120
90
60
30
50
B-37