5.6 GROUPED ELEMENTS
e) AUXILIARY UNDERVOLTAGE (ANSI 27X)

PATH: SETTINGS
GROUPED ELEMENTS
 AUXILIARY UV1
5
The T60 contains one auxiliary undervoltage element for each VT bank. This element is intended for monitoring undervolt-
age conditions of the auxiliary voltage. The
ment starts timing. The nominal secondary voltage of the auxiliary voltage channel entered under

SETUP
AC INPUTS
pickup level.
The
setting selects the minimum operating time of the auxiliary undervoltage element. Both
AUX UV1 DELAY
and
settings establish the operating curve of the undervoltage element. The auxiliary undervoltage element
AUX UV1 DELAY
can be programmed to use either definite time delay or inverse time delay characteristics. The operating characteristics
and equations for both definite and inverse time delay are as for the phase undervoltage element.
The element resets instantaneously. The minimum voltage setting selects the operating voltage below which the element is
blocked.
SETTING
AUX UV1
FUNCTION:
Disabled=0
Enabled=1
SETTING
AUX UV1 BLOCK:
Off=0
SETTING
AUX UV1 SIGNAL
SOURCE:
AUX VOLT Vx
5-222
SETTING GROUP 1(6)
AUX UV1
FUNCTION: Disabled
AUX UV1 SIGNAL
MESSAGE
SOURCE: SRC 1
AUX UV1 PICKUP:
MESSAGE
0.700 pu
AUX UV1 CURVE:
MESSAGE
Definite Time
AUX UV1 DELAY:
MESSAGE
1.00 s
AUX UV1 MINIMUM:
MESSAGE
VOLTAGE: 0.100 pu
AUX UV1 BLOCK:
MESSAGE
Off
AUX UV1 TARGET:
MESSAGE
Self-reset
AUX UV1 EVENTS:
MESSAGE
Disabled
AUX UV1 PICKUP

VOLTAGE BANK X5
AUXILIARY VT X5 SECONDARY
SETTING
AUX UV1 MINIMUM
VOLTAGE:
<
Vx Minimum
Figure 5–120: AUXILIARY UNDERVOLTAGE SCHEME LOGIC
T60 Transformer Protection System


VOLTAGE ELEMENTS
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: 0.000 to 3.000 pu in steps of 0.001
Range: Definite Time, Inverse Time
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.000 to 3.000 pu in steps of 0.001
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
selects the voltage level at which the time undervoltage ele-
is the per-unit base used when setting the
SETTING
AUX UV1 PICKUP:
AUX UV1 CURVE:
AUX UV1 DELAY:
<
RUN
Vx Pickup
AND
t
V
5 SETTINGS
AUXILIARY UV1(2)

SETTINGS
SYSTEM
AUX UV1 PICKUP
FLEXLOGIC OPERANDS
AUX UV1 PKP
AUX UV1 DPO
AUX UV1 OP
827849A2.CDR