User-Programmable Self Tests - GE UR T60 Instruction Manual

Ur series transformer protection system
Table of Contents

Advertisement

5.2 PRODUCT SETUP
See the figure in the Setting Groups section of the Control Elements section later in this chapter for an example of group
activation.
PATH: SETTINGS
PRODUCT SETUP
 USER-PROGRAMMABLE
 SELF TESTS
5
All major self-test alarms are reported automatically with their corresponding FlexLogic™ operands, events, and targets.
Most of the minor alarms can be disabled if desired.
When in the "Disabled" mode, minor alarms will not assert a FlexLogic™ operand, write to the event recorder, or display
target messages. Moreover, they will not trigger the
mode, minor alarms continue to function along with other major and minor alarms. Refer to the Relay self-tests section in
chapter 7 for additional information on major and minor self-test alarms.
To enable the Ethernet switch failure function, ensure that the
menu.
NOTE
5-52


USER-PROGRAMMABLE SELF TESTS

DIRECT RING BREAK
FUNCTION: Enabled
DIRECT DEVICE OFF
MESSAGE
FUNCTION: Enabled
REMOTE DEVICE OFF
MESSAGE
FUNCTION: Enabled
PRI. ETHERNET FAIL
MESSAGE
FUNCTION: Disabled
SEC. ETHERNET FAIL
MESSAGE
FUNCTION: Disabled
BATTERY FAIL
MESSAGE
FUNCTION: Enabled
SNTP FAIL
MESSAGE
FUNCTION: Enabled
IRIG-B FAIL
MESSAGE
FUNCTION: Enabled
ETHERNET SWITCH FAIL
MESSAGE
FUNCTION: Disabled
ANY MINOR ALARM
T60 Transformer Protection System
5.2.12 USER-PROGRAMMABLE SELF TESTS
Range: Disabled, Enabled. Valid for units equipped with
Direct Input/Output module.
Range: Disabled, Enabled. Valid for units equipped with
Direct Input/Output module.
Range: Disabled, Enabled. Valid for units that contain a
CPU with Ethernet capability.
Range: Disabled, Enabled. Valid for units that contain a
CPU with a primary fiber port.
Range: Disabled, Enabled. Valid for units that contain a
CPU with a redundant fiber port.
Range: Disabled, Enabled.
Range: Disabled, Enabled. Valid for units that contain a
CPU with Ethernet capability.
Range: Disabled, Enabled.
Range: Disabled, Enabled.
or
messages. When in the "Enabled"
ANY SELF-TEST
ETHERNET SWITCH FAIL FUNCTION
5 SETTINGS
is "Enabled" in this
GE Multilin