B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 8 of 65)
ADDR
REGISTER NAME
21E8
Breaker 1 Operating Time Phase C
21E9
Breaker 1 Operating Time
21EA
...Repeated for Breaker Arcing Current 2
21F4
...Repeated for Breaker Arcing Current 3
21FE
...Repeated for Breaker Arcing Current 4
B
Breaker Arcing Current Commands (Read/Write Command) (4 modules)
2224
Breaker 1 Arcing Current Clear Command
2225
Breaker 2 Arcing Current Clear Command
2226
Breaker 3 Arcing Current Clear Command
2227
Breaker 4 Arcing Current Clear Command
Passwords Unauthorized Access (Read/Write Command)
2230
Reset Unauthorized Access
Transformer Differential and Restraint (Read Only)
2300
Transformer Reference Winding
2301
Transformer Differential Phasor Iad Magnitude
2302
Transformer Differential Phasor Iad Angle
2303
Transformer Restraint Phasor Iar Magnitude
2304
Transformer Restraint Phasor Iar Angle
2305
Transformer Differential 2nd Harm Iad Magnitude
2306
Transformer Differential 2nd Harm Iad Angle
2307
Transformer Differential 5th Harm Iad Magnitude
2308
Transformer Differential 5th Harm Iad Angle
2309
Transformer Differential Phasor Ibd Magnitude
230A
Transformer Differential Phasor Ibd Angle
230B
Transformer Restraint Phasor Ibr Magnitude
230C
Transformer Restraint Phasor Ibr Angle
230D
Transformer Differential 2nd Harm Ibd Magnitude
230E
Transformer Differential 2nd Harm Ibd Angle
230F
Transformer Differential 5th Harm Ibd Magnitude
2310
Transformer Differential 5th Harm Ibd Angle
2311
Transformer Differential Phasor Icd Magnitude
2312
Transformer Differential Phasor Icd Angle
2313
Transformer Restraint Phasor Icr Magnitude
2314
Transformer Restraint Phasor Icr Angle
2315
Transformer Differential 2nd Harm Icd Magnitude
2316
Transformer Differential 2nd Harm Icd Angle
2317
Transformer Differential 5th Harm Icd Magnitude
2318
Transformer Differential 5th Harm Icd Angle
Transformer Thermal Inputs Actual Values (Read Only)
2330
Transformer Top Oil Temperature
2331
Transformer Hottest Spot Temperature
2332
Transformer Aging Factor
2333
Transformer Daily Loss of Life
Transformer Thermal Inputs Actual Values (Read Only Non-Volatile)
2335
Transformer Loss of Life
Synchrocheck Actual Values (Read Only) (2 modules)
2400
Synchrocheck 1 Delta Voltage
2402
Synchrocheck 1 Delta Frequency
2403
Synchrocheck 1 Delta Phase
2404
...Repeated for Synchrocheck 2
Filed Unit Raw Data Settings (Read/Write Setting)
2460
Field Raw Data Port
2461
Filed Raw Data Freeze
B-16
RANGE
0 to 65535
0 to 65535
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
1 to 6
0 to 30
-359.9 to 0
0 to 30
-359.9 to 0
0 to 999.9
-359.9 to 0
0 to 999.9
-359.9 to 0
0 to 30
-359.9 to 0
0 to 30
-359.9 to 0
0 to 999.9
-359.9 to 0
0 to 999.9
-359.9 to 0
0 to 30
-359.9 to 0
0 to 30
-359.9 to 0
0 to 999.9
-359.9 to 0
0 to 999.9
-359.9 to 0
0 to 300
0 to 300
0 to 6553.5
0 to 500000
0 to 500000
-1000000000000 to
1000000000000
0 to 655.35
0 to 359.9
0 to 7
0 to 1
T60 Transformer Protection System
APPENDIX B
UNITS
STEP
FORMAT
ms
1
F001
ms
1
F001
---
1
F126
---
1
F126
---
1
F126
---
1
F126
---
1
F126
---
1
F001
pu
0.001
F001
degrees
0.1
F002
pu
0.001
F001
degrees
0.1
F002
% fo
0.1
F001
degrees
0.1
F002
% fo
0.1
F001
degrees
0.1
F002
pu
0.001
F001
degrees
0.1
F002
pu
0.001
F001
degrees
0.1
F002
% fo
0.1
F001
degrees
0.1
F002
% fo
0.1
F001
degrees
0.1
F002
pu
0.001
F001
degrees
0.1
F002
pu
0.001
F001
degrees
0.1
F002
% fo
0.1
F001
degrees
0.1
F002
% fo
0.1
F001
degrees
0.1
F002
°C
1
F002
°C
1
F002
PU
0.1
F001
Hours
1
F060
Hours
1
F060
V
1
F060
Hz
0.01
F001
degrees
0.1
F001
---
1
F244
---
1
F102
DEFAULT
0
0
0 (No)
0 (No)
0 (No)
0 (No)
0 (No)
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
6 (H1a)
0 (Disabled)