5.2 PRODUCT SETUP
The MMXU deadband settings represent the deadband values used to determine when the update the MMXU "mag" and
"cVal" values from the associated "instmag" and "instcVal" values. The "mag" and "cVal" values are used for the IEC 61850
buffered and unbuffered reports. These settings correspond to the associated "db" data items in the CF functional con-
straint of the MMXU logical node, as per the IEC 61850 standard. According to IEC 61850-7-3, the db value "shall repre-
sent the percentage of difference between the maximum and minimum in units of 0.001%". Thus, it is important to know the
maximum value for each MMXU measured quantity, since this represents the 100.00% value for the deadband.
The minimum value for all quantities is 0; the maximum values are as follows:
phase current: 46 × phase CT primary setting
neutral current: 46 × ground CT primary setting
voltage: 275 × VT ratio setting
power (real, reactive, and apparent): 46 × phase CT primary setting × 275 × VT ratio setting
frequency: 90 Hz
power factor: 2
The GGIO1 status configuration points are shown below:
PATH: SETTINGS
PRODUCT SETUP
 GGIO1 STATUS
 CONFIGURATION
5
The
NUMBER OF STATUS POINTS IN GGIO1
instantiated in the GGIO1 logical node. Changes to the
the T60 is restarted.
The GGIO2 control configuration points are shown below:
PATH: SETTINGS
PRODUCT SETUP
GGIO2 CF SPSCO 1(64)
 GGIO2 CF SPCSO 1
The GGIO2 control configuration settings are used to set the control model for each input. The available choices are "0"
(status only), "1" (direct control), and "2" (SBO with normal security). The GGIO2 control points are used to control the T60
virtual inputs.
5-32

COMMUNICATIONS
NUMBER OF STATUS
POINTS IN GGIO1: 8
GGIO1 INDICATION
MESSAGE
Off
GGIO1 INDICATION
MESSAGE
Off
GGIO1 INDICATION
MESSAGE
Off
GGIO1 INDICATION 128
MESSAGE
Off
setting specifies the number of "Ind" (single point status indications) that are

COMMUNICATIONS
GGIO2 CF SPCSO 1
CTLMODEL: 1
T60 Transformer Protection System


IEC 61850 PROTOCOL
Range: 8 to 128 in steps of 8
Range: FlexLogic™ operand
1
Range: FlexLogic™ operand
2
Range: FlexLogic™ operand
3
Range: FlexLogic™ operand
NUMBER OF STATUS POINTS IN GGIO1


IEC 61850 PROTOCOL
Range: 0, 1, or 2
5 SETTINGS
GGIO1 STATUS CONFIGURATION
setting will not take effect until
GGIO2 CONTROL CONFIGURATION