5.6 GROUPED ELEMENTS
c) INSTANTANEOUS DIFFERENTIAL

PATH: SETTINGS
GROUPED ELEMENTS
 INSTANTANEOUS
 DIFFERENTIAL
The instantaneous differential element acts as an instantaneous overcurrent element responding to the measured differen-
tial current magnitude (filtered fundamental frequency component) and applying a user-selectable pickup threshold. The
pickup threshold should be set greater than the maximum spurious differential current that could be encountered under
non-internal fault conditions (typically magnetizing inrush current or an external fault with extremely severe CT saturation).
SETTING
INST DIFFERENTIAL
FUNCTION:
Disabled=0
5
Enabled=1
SETTING
INST DIFF BLOCK:
Off=0
ACTUAL VALUE
DIFF PHASOR
Iad
Ibd
Icd
d) HOTTEST-SPOT TEMPERATURE

PATH: SETTINGS
GROUPED ELEMENTS
 HOTTEST-SPOT
 TEMPERATURE
The Hottest-Spot Temperature element provides a mechanism for detecting abnormal winding hottest-spot temperatures
inside the transformer. It can be set to alarm or trip in cases where the computed hottest-spot temperature is above the
pickup threshold for a user-specified time (considered as transformer overheating).
5-178
SETTING GROUP 1(6)
INST DIFFERENTIAL
FUNCTION: Disabled
INST DIFFERENTIAL
MESSAGE
PICKUP:
INST DIFF BLOCK:
MESSAGE
Off
INST DIFFERENTIAL
MESSAGE
TARGET: Self-reset
INST DIFFERENTIAL
MESSAGE
EVENTS: Disabled
AND
Figure 5–91: INSTANTANEOUS DIFFERENTIAL SCHEME LOGIC
SETTING GROUP 1(6)
XFMR HST FUNCTION:
Disabled
XFMR HST PICKUP:
MESSAGE
140°C
XFMR HST DELAY:
MESSAGE
1 min.
XFMR HST BLOCK:
MESSAGE
Off
XFMR HST TARGET:
MESSAGE
Self-Reset
T60 Transformer Protection System

TRANSFORMER
Range: Disabled, Enabled
Range: 2.000 to 30.000 pu in steps of 0.001
8.000 pu
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
SETTING
INST DIFFERENTIAL
PICKUP:
RUN
Iad > PICKUP
RUN
Ibd > PICKUP
OR
RUN
Icd > PICKUP

TRANSFORMER
Range: Disabled, Enabled
Range: 50 to 300°C in steps of 1
Range: 0 to 30000 min. in steps of 1
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
5 SETTINGS
INSTANTANEOUS DIFFERENTIAL
FLEXLOGIC OPERANDS
XFMR INST DIFF OP A
XFMR INST DIFF OP B
XFMR INST DIFF OP C
FLEXLOGIC OPERAND
XFMR INST DIFF OP
828000A1.CDR