5.9 TRANSDUCER INPUTS AND OUTPUTS
It is recommended to use the T60 to configure the RRTD parameters. If the RRTDPC software is used to change the RRTD
settings directly (the application and type settings), then one of the following two operations is required for changes to be
reflected in the T60.
Cycle power to T60.
Break then re-establish the communication link between the RRTD unit and the T60. This will cause the
operand to be asserted then de-asserted.
FAIL
b) REMOTE RTDS 1 THROUGH 12

PATH: SETTINGS
TRANSDUCER I/O
 RRTD 1
5
The remote RTD inputs convert values of input resistance into temperature for further operations. These inputs are
intended to be connected to any of the RTD types in common use. Specific hardware details are contained in chapter 3.
On power up, the T60 reads and saves all application and type settings from the RRTD. This synchronizes the RRTD and
T60. Any changes to RRTD settings (function, application, or type) from the T60 interface are immediately reflected in the
RRTD. The following rules are followed.
If the
RRTD 1 FUNCTION
If the
RRTD 1 FUNCTION
If the
RRTD 1 APPLICATION
RRTD device.
5-286

RRTD INPUTS
RRTD 1 FUNCTION:
Disabled
RRTD 1 ID:
MESSAGE
RRTD 1
RRTD 1 TYPE:
MESSAGE
100 Ω Platinum
RRTD 1
MESSAGE
APPLICATION: None
RRTD 1 ALARM
MESSAGE
TEMPERATURE: 130°C
RRTD 1 ALARM
MESSAGE
PKP DELAY: 5 s
RRTD 1 TRIP
MESSAGE
TEMPERATURE: 130°C
RRTD 1 TRIP
MESSAGE
PKP DELAY: 5 s
RRTD 1 TRIP
MESSAGE
RST DELAY: 5 s
RRTD 1 TRIP VOTING:
MESSAGE
None
RRTD 1 OPEN:
MESSAGE
None
RRTD 1 BLOCK:
MESSAGE
Off
RRTD 1 TARGET:
MESSAGE
Self-reset
RRTD 1 EVENTS:
MESSAGE
Disabled
setting is "Enabled", then the
setting is "Disabled", then
or
settings are changes, then these settings are immediately written to the
RRTD 1 TYPE
T60 Transformer Protection System

RRTD RTD 1(12)
Range: Disabled, Enabled
Range: Up to 20 alphanumeric characters
Range: 100 Ω Nickel, 10 Ω Copper, 100 Ω Platinum,
120 Ω Nickel
Range: None, Stator, Bearing, Ambient, Group 1,
Group 2
Range: 1 to 200°C in steps of 1
Range: 5 to 600 s in steps of 5
Range: 1 to 200°C in steps of 1
Range: 5 to 600 s in steps of 5
Range: 5 to 600 s in steps of 5
Range: None, Group, Remote RTD 1, Remote RTD 2,...,
Remote RTD 12
Range: None, Alarm, Block
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
setting value will be written to RRTD device.
RRTD 1 APPLICATION
setting value is set as "None".
RRTD1 APPLICATION
5 SETTINGS
RRTD COMM
GE Multilin