GE UR T60 Instruction Manual page 574

Ur series transformer protection system
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 28 of 65)
ADDR
REGISTER NAME
5E70
...Repeated for Ground Instantaneous Overcurrent 8
5E80
...Repeated for Ground Instantaneous Overcurrent 9
5E90
...Repeated for Ground Instantaneous Overcurrent 10
5EA0
...Repeated for Ground Instantaneous Overcurrent 11
5EB0
...Repeated for Ground Instantaneous Overcurrent 12
B
Setting Groups (Read/Write Setting)
5F80
Setting Group for Modbus Comms (0 means group 1)
5F81
Setting Groups Block
5F82
FlexLogic Operands to Activate Groups 2 through 6 (5
items)
5F89
Setting Group Function
5F8A
Setting Group Events
Setting Groups (Read Only)
5F8B
Current Setting Group
Setting Group Names (Read/Write Setting)
5F8C
Setting Group 1 Name
5F94
Setting Group 2 Name
5F9C
Setting Group 3 Name
5FA4
Setting Group 4 Name
5FAC
Setting Group 5 Name
5FB4
Setting Group 6 Name
Transformer Hottest Spot (Read/Write Grouped Setting)
6140
Transformer Hottest Spot Function
6141
Transformer Hottest Spot Pickup
6142
Transformer Hottest Spot Delay
6143
Transformer Hottest Spot Block
6144
Transformer Hottest Spot Target
6145
Transformer Hottest Spot Events
Transformer Aging Factor (Read/Write Grouped Setting)
6150
Transformer Aging Factor Function
6151
Transformer Aging Factor Pickup
6152
Transformer Aging Factor Delay
6153
Transformer Aging Factor Block
6154
Transformer Aging Factor Target
6155
Transformer Aging Factor Events
Transformer Loss of Life (Read/Write Grouped Setting)
6160
Transformer Loss of Life Function
6161
XFMR LOL Initial Value
6163
Transformer Loss of Life Pickup
6165
Transformer Loss of Life Block
6166
Transformer Loss of Life Target
6167
Transformer Loss of Life Events
Transformer Thermal Inputs (Read/Write Setting)
6170
Transformer Thermal Model Source Input
6171
Ambient Temperature Input Sensor
6172
Top Oil Temperature Input Sensor
6173
January Average Ambient Temperature
6174
February Average Ambient Temperature
6175
March Average Ambient Temperature
6176
April Average Ambient Temperature
6177
May Average Ambient Temperature
6178
June Average Ambient Temperature
6179
July Average Ambient Temperature
617A
August Average Ambient Temperature
B-36
RANGE
0 to 5
0 to 65535
0 to 65535
0 to 1
0 to 1
0 to 5
---
---
---
---
---
---
0 to 1
50 to 300
0 to 30000
0 to 65535
0 to 2
0 to 1
0 to 1
1 to 10
0 to 30000
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 500000
0 to 500000
0 to 65535
0 to 2
0 to 1
0 to 5
0 to 32
0 to 32
-60 to 60
-60 to 60
-60 to 60
-60 to 60
-60 to 60
-60 to 60
-60 to 60
-60 to 60
T60 Transformer Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F001
---
1
F300
---
1
F300
---
1
F102
---
1
F102
---
1
F001
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
1
F102
°C
1
F001
min
1
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F102
PU
0.1
F001
min
1
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F102
hrs
1
F003
hrs
1
F003
---
1
F300
---
1
F109
---
1
F102
---
1
F167
---
1
F450
---
1
F460
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
°C
1
F002
DEFAULT
0
0
0
0 (Disabled)
0 (Disabled)
0
(none)
(none)
(none)
(none)
(none)
(none)
0 (Disabled)
140
1
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
20
10
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0
180000
0
0 (Self-reset)
0 (Disabled)
0 (SRC 1)
0
0
-20
-30
-10
10
20
30
30
30