GE UR T60 Instruction Manual page 160

Ur series transformer protection system
Table of Contents

Advertisement

5.2 PRODUCT SETUP
When the DNP data points (analog inputs and/or binary inputs) are configured for Ethernet-enabled relays,
check the "DNP Points Lists" T60 web page to view the points lists. This page can be viewed with a web
NOTE
browser by entering the T60 IP address to access the T60 "Main Menu", then by selecting the "Device Infor-
mation Menu" > "DNP Points Lists" menu item.
The
DNP OBJECT 1 DEFAULT VARIATION
default variation number for object types 1, 2, 20, 21, 22, 23, 30, and 32. The default variation refers to the variation
response when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. Refer to the DNP implementation section in
appendix E for additional details.
The DNP binary outputs typically map one-to-one to IED data points. That is, each DNP binary output controls a single
physical or virtual control point in an IED. In the T60 relay, DNP binary outputs are mapped to virtual inputs. However, some
legacy DNP implementations use a mapping of one DNP binary output to two physical or virtual control points to support
the concept of trip/close (for circuit breakers) or raise/lower (for tap changers) using a single control point. That is, the DNP
master can operate a single point for both trip and close, or raise and lower, operations. The T60 can be configured to sup-
port paired control points, with each paired control point operating two virtual inputs. The
setting allows configuration of from 0 to 32 binary output paired controls. Points not configured as paired operate on
POINTS
a one-to-one basis.
The
setting is the DNP slave address. This number identifies the T60 on a DNP communications link. Each
DNP ADDRESS
DNP slave should be assigned a unique address.
The
DNP TCP CONNECTION TIMEOUT
there is no data traffic on a DNP TCP connection for greater than the time specified by this setting, the connection will be
aborted by the T60. This frees up the connection to be re-used by a client.
Relay power must be re-cycled after changing the
effect.
5
NOTE
f) DNP / IEC 60870-5-104 POINT LISTS
PATH: SETTINGS
PRODUCT SETUP
 DNP / IEC104
 POINT LISTS
The binary and analog inputs points for the DNP protocol, or the MSP and MME points for IEC 60870-5-104 protocol, can
configured to a maximum of 256 points. The value for each point is user-programmable and can be configured by assigning
FlexLogic™ operands for binary inputs / MSP points or FlexAnalog parameters for analog inputs / MME points.
The menu for the binary input points (DNP) or MSP points (IEC 60870-5-104) is shown below.
PATH: SETTINGS
PRODUCT SETUP
 BINARY INPUT / MSP
 POINTS
Up to 256 binary input points can be configured for the DNP or IEC 60870-5-104 protocols. The points are configured by
assigning an appropriate FlexLogic™ operand. Refer to the Introduction to FlexLogic™ section in this chapter for the full
range of assignable operands.
The menu for the analog input points (DNP) or MME points (IEC 60870-5-104) is shown below.
5-22
to
DNP OBJECT 32 DEFAULT VARIATION
setting specifies a time delay for the detection of dead network TCP connections. If

COMMUNICATIONS
 BINARY INPUT / MSP
 POINTS
 ANALOG INPUT / MME
MESSAGE
 POINTS

COMMUNICATIONS
Point:
Off
Point:
MESSAGE
Off
Point:
MESSAGE
Off
T60 Transformer Protection System
settings allow the user to select the DNP
DNP TCP CONNECTION TIMEOUT

DNP / IEC104 POINT LISTS
Range: see sub-menu below
Range: see sub-menu below

DNP / IEC104 POINT LISTS
Range: FlexLogic™ operand
0
Range: FlexLogic™ operand
1
Range: FlexLogic™ operand
255
5 SETTINGS
DNP NUMBER OF PAIRED CONTROL
setting for the changes to take
BINARY INPUT / MSP POINTS
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents