Environmental Type Tests - Siemens RUGGEDCOM RSG2100 Installation Manual

Hide thumbs Also See for RUGGEDCOM RSG2100:
Table of Contents

Advertisement

RUGGEDCOM RSG2100
Installation Guide
Radiated RFI
Fast Transient
Oscillatory
HV Impulse
Dielectric Strength
Damped Oscillatory
Magnetic Field

Environmental Type Tests

Test
IEC 60068-2-1
IEC 60068-2-2
IEC
Humidity (Damp Heat, Cyclic)
60068-2-30
IEC
60068-21-1
IEC
60068-21-2
IEC
60068-2-78
IEC
Change of Temperature
60068-2-14
IEC
60255-21-2
IEC
60255-21-3
EMC and Environmental Type Tests
Description
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Enclosure Ports
Description
Cold Temperature
Dry Heat
Vibration
Shock
Humidity (Damp
Heat, Steady State)
Bump
Seismic
Test Levels
Test Ad
-40 °C (-40 °F), 16 Hours
Test Bd
85 °C (185 °F), 16 Hours
Test Db
95% (non-condensing),
55 °C (131 °F), 6 cycles
2g @ 10-150 Hz
30 g @ 11 ms
Test Cab
10 days @ 55 °C (131 °F)
and 93% Relative Humidity
Test Nb
5 Cycles, -40 to 85°
C (40 to 185° F)
10 g @ 16 ms
Method A, Class 2
Test Levels
±8 kV
±15 kV
35 V/m
4 kV @ 2.5 kHz
4 kV
4 kV
4 kV
2.5 kV Common Mode @ 1 MHz
2.5 kV Common
1 kV differential mode @ 1 MHz
2.5 kV Common
1 kV differential mode @ 1 MHz
5 kV (Fail-Safe Relay Output)
5 kV
5 kV
2 kV
2 kV
2 kV
100 A/m
Severity Level
Chapter 6
Certification
Class 1
Class 1
45