System 300S
Take IP address parame-
ters in project

5.7 Hardware configuration - Communication

5.8 Setting standard CPU parameters

5.8.1 Parameterization via Siemens CPU

Parameterization via Sie-
mens CPU
HB140 | CPU | 315-4PN23 | en | 18-02
Setting standard CPU parameters > Parameterization via Siemens CPU
1.
Open the Siemens hardware configurator und configure the Siemens CPU 315-2
PN/DP (6ES7 315-2EH14-0AB0 V3.2).
2.
Configure the modules at the standard bus.
3.
For the Ethernet PG/OP channel you have to configure a Siemens CP 343-1
(SIMATIC 300 \ CP 300 \ Industrial Ethernet \CP 343-1 \ 6GK7 343-1EX11 0XE0)
always below the really plugged modules.
4.
Open the property window via double-click on the CP 343-1EX11 and enter for the
CP at 'Properties' the IP address data, which you have assigned before.
5.
Assign the CP to a 'Subnet' . Without assignment the IP address data are not used!
6.
Transfer your project.
The hardware configuration is described at the following pages:
Ä Chap. 7.4 'Deployment as PROFIBUS DP master' page 93
Ä Chap. 7.5 'Deployment as PROFIBUS DP slave' page 94
Ä Chap. 6.3 'Deployment of RS485 interface for PtP' page 77
Since the CPU is to be configured as Siemens CPU 315-2 PN/DP (6ES7
315-2EH14-0AB0 V3.2) in the Siemens hardware configurator, the standard parameters
of the VIPA CPU may be set with "Object properties" of the CPU during hardware confi-
guration. Via a double-click on the CPU 315-2 PN/DP (6ES7 315-2EH14-0AB0 V3.2) the
parameter window of the CPU may be accessed. Using the registers you get access to
every standard parameter of the CPU.