Emerson Unidrive M100 Control User Manual page 93

Variable speed ac drive for induction motors
Hide thumbs Also See for Unidrive M100:
Table of Contents

Advertisement

Safety
Product
Mechanical
information
information
installation
Trip
rS
Measured resistance has exceeded the parameter range
The rS trip indicates that the measured stator resistance of the motor during an autotune test has exceeded the maximum
possible value of Stator Resistance (05.017).
If the measured value or a value written to this parameter by the user exceeds (V
where V
The stationary autotune is initiated using the autotune function (Pr 05.012) or in open loop vector mode (Pr 05.014) on the
first run command after power up in mode 4 (Ur_I) or on every run command in modes 0 (Ur_S) or 3 (Ur_Auto). This trip
can occur if the motor is very small in comparison to the rating of the drive.
If the value is the result of a measurement made by the drive then sub-trip 0 is applied, or if it is because the parameter has
been changed by the user then sub-trip 3 is applied. During the stator resistance section of auto-tuning an additional test is
performed to measure the drive inverter characteristics to provide the compensation necessary for dead-times. If the
inverter characteristic measurement fails then sub-trip 2 is applied.
The reason for the trip can be identified by the sub-trip number.
33
Recommended actions:
Check that a value has not been entered in the stator resistance for the presently selected motor map that exceeds the
allowed range.
Check the motor cable / connections
Check the integrity of the motor stator winding using a insulation tester
Check the motor phase to phase resistance at the drive terminals
Check the motor phase to phase resistance at the motor terminals
Ensure the stator resistance of the motor falls within the range of the drive model
Select fixed boost mode (Pr 05.014 = Fd) and verify the output current waveforms with an oscilloscope
Replace the motor
So.St
Soft start relay failed to close, soft start monitor failed
The So.St trip indicates that the soft start relay in the drive failed to close or the soft start monitoring circuit has failed.
The cause of the trip can be identified by the sub-trip number.
226
Recommended actions:
Hardware fault – Contact the supplier of the drive
St.HF
Hardware trip has occurred during last power down
The St.HF trip indicates that a hardware trip (HF01 –HF18) has occurred and the drive has been power cycled. The sub-trip
number identifies the HF trip.
221
Recommended actions:
Enter 1299 in Pr mm.000 and press reset to clear the trip
Sto
No Safe Torque Off board fitted
Internal STO board not fitted correctly
234
Recommended actions:
Hardware fault – Contact the supplier of the drive
th.br
Brake resistor over temperature
The th.br trip is initiated if the hardware based braking resistor thermal monitoring is connected and the resistor overheats.
If the braking resistor is not used, then this trip must be disabled with bit 3 of Action On Trip Detection (10.037) to prevent
this trip.
10
Recommended actions:
Check brake resistor wiring
Check braking resistor value is greater than or equal to the minimum resistance value
Check braking resistor insulation
Unidrive M100 / M101 Control User Guide
Issue Number: 1
Electrical
Getting
installation
started
parameters
is the full scale DC bus voltage then this trip is initiated.
FS
Sub-trip
Stator resistance (5.017) test failed during Autotune or measured stator resistance value is out of
0
range.
1
Reserved
Transient inductance (5.024) test failed during Autotune or measured stator resistance value is out
2
of range.
3
The value of Stator Resistance (05.017) is too large when the parameter is edited.
Stator resistance (5.017) test successful during Autotune but Pr 05.017 is too large for this drive
4
current and voltage rating.
Sub-trip
1
Soft-start failure
2
DC bus capacitor failure on 110 V drive
Basic
Running the
Optimization
motor
Diagnosis
Reason
Reason
Advanced
NV Media Card
Diagnostics
parameters
/√2) / Full Scale Current Kc (11.061),
FS
UL Listing
93

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Unidrive m101

Table of Contents