Emerson Unidrive M100 Control User Manual page 15

Variable speed ac drive for induction motors
Hide thumbs Also See for Unidrive M100:
Table of Contents

Advertisement

Safety
Product
Mechanical
information
information
installation
9
+24 V user output
Default function
Voltage tolerance
Maximum output current
Protection
10
Digital I/O 1
Default function
Type
Input / output mode controlled by ...
Operating as in input
Absolute maximum applied voltage range
Impedance
Input threshold
Operating as an output
Nominal maximum output current
Maximum output current
Common to all modes
Voltage range
Sample rate
11
Digital Input 2
12
Digital Input 3
13
Digital Input 4
Terminal 11 default function
Terminal 12 default function
Terminal 13 default function
Type
Voltage range
Absolute maximum applied voltage range
Impedance
Input threshold
Sample rate
41
Relay contacts
42
Default function
Contact voltage rating
Contact maximum current rating
Contact minimum recommended rating
Contact type
Default contact condition
Update rate
To prevent the risk of a fire hazard in the event of a fault, a fuse or other over-current protection must be installed in the relay circuit.
WARNING
Unidrive M100 / M101 Control User Guide
Issue Number: 1
Electrical
Getting
Basic
installation
started
parameters
Supply for external digital devices
±20 %
100 mA
Current limit and trip
AT ZERO FREQUENCY output
Positive logic digital input, positive logic voltage source output.
PWM or frequency output modes can be selected.
Pr 08.031
-8 V to +30 V relative to 0V
6.8 kΩ
10 V ±0.8 V (IEC 61131-2)
50 mA
100 mA (total including +24 Vout)
0V to +24 V
1 ms when routed to destinations Pr 06.035 or Pr 06.036, otherwise 4 ms
DRIVE ENABLE input
RUN FORWARD input
RUN REVERSE input
Positive logic only digital inputs
0V to +24 V
-18 V to +30 V relative to 0V
6.8 kΩ
10 V ±0.8 V (IEC 61131-2)
1 ms when routed to destinations Pr 06.035 or Pr 06.036, otherwise 4 ms.
Drive OK indicator
240 Vac, Installation over-voltage category II
2 A AC 240 V
4 A DC 30 V resistive load
0.5 A DC 30 V inductive load (L/R = 40 ms)
12 V 100 mA
Normally open
Closed when power applied and drive OK
1 ms
Running the
Optimization
NV Media Card
motor
Advanced
Diagnostics
UL Listing
parameters
15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Unidrive m101

Table of Contents