Trip
Out.P
Output phase loss detected
The Out.P trip indicates that phase loss has been detected at the drive output.
Sub-trip
98
NOTE
If Pr 05.042 = 1, the physical output phases are reversed, and so sub-trip 3 refers to physical output phase V and sub-trip 2
refers to physical output phase W.
Recommended actions:
•
Check motor and drive connections
•
To disable the trip set Output Phase Loss Detection Enable (06.059) = 0
OV
DC bus voltage has exceeded the peak level or maximum continuous level for 15 seconds
The OV trip indicates that the DC bus voltage has exceeded the VM_DC_VOLTAGE[MAX] or
VM_DC_VOLTAGE_SET[MAX] for 15 s. The trip threshold varies depending on voltage rating of the drive as shown below.
Voltage rating
Sub-trip Identification
Source
Control
2
system
Control
system
Power
system
Recommended actions:
•
Increase deceleration ramp (Pr 00.004)
•
Decrease the braking resistor value (staying above the minimum value)
•
Check nominal AC supply level
•
Check for supply disturbances which could cause the DC bus to rise
•
Check motor insulation using an insulation tester
90
Electrical
Getting
installation
started
parameters
1
U phase detected as disconnected when drive enabled to run.
2
V phase detected as disconnected when drive enabled to run.
3
W phase detected as disconnected when drive enabled to run.
The drive output frequency is above 4 Hz and a phase is disconnected for the time
4
specified by Output Phase Loss Detection Time (06.058).
VM_DC_VOLTAGE[MAX]
100
510
200
510
400
870
xx
y
00
0
00
0
01
0
Basic
Running the
Optimization
motor
Diagnosis
Reason
VM_DC_VOLTAGE_SET[MAX]
400
400
800
01: Instantaneous trip when the DC bus voltage exceeds
VM_DC_VOLTAGE[MAX].
02: Time delayed trip indicating that the DC bus voltage is above
VM_DC_VOLTAGE_SET[MAX].
00: Instantaneous trip when the DC bus voltage exceeds
VM_DC_VOLTAGE[MAX].
Advanced
NV Media Card
Diagnostics
parameters
zz
Unidrive M100 / M101 Control User Guide
UL Listing
Issue Number: 1