Download Print this page
Emerson Fisher MR98 Series Installation Manual

Emerson Fisher MR98 Series Installation Manual

Ad2000 compliant
Hide thumbs Also See for Fisher MR98 Series:

Advertisement

Quick Links

Installation Guide
D104615X014
April 2022
Introduction
This Installation Guide provides instructions for
installation, startup and adjustment. To receive a
copy of the Instruction Manual, contact your local
Sales Office or view a copy at www.emerson.
com. For further information, refer to MR98 Series
Backpressure Regulators and Relief valves Instruction
Manual, D104615X012 (D.A.CH. Region Only).
PED Category
This product may be used as a safety accessory
with pressure equipment in the following Pressure
Equipment Directive. It may also be used outside
of the Pressure Equipment Directive using Sound
Engineering Practice (SEP) per table below. For
information on the current PED revision, see Bulletin:
D103053X012 (D.A.CH. Region Only).
Specifications
TYPE
PRODUCT SIZE
MR98H/
DN 15 to 25 /
MR98HH
1/2 to 1 in.
DN 40 and 50 /
MR98H
1-1/2 and 2 in.
Available Constructions
Type MR98H: Backpressure regulator/relief valve
for spring settings range from 0.34 to 13.8 bar /
5 to 200 psig.
Type MR98HH: Backpressure regulator/relief
valve for spring settings range from 10.3 to
25.9 bar / 150 to 375 psig.
Body and Orifice Sizes
DN 15 / 1/2 in. body: 10.56 mm / 0.416 in. orifice
DN 20 and 25 / 3/4 and 1 in. bodies:
16.02 mm / 0.631 in. orifice
DN 40 and 50 / 1-1/2 and 2 in. bodies:
29 mm / 1.142 in. orifice
End Connection Styles
G Thread and Integral PN 16/25/40 RF; all
flanged sizes are fabricated with a 356 mm / 14 in.
face-to-face dimension.
Set Pressure Ranges
(1)
See Table 1
1. The pressure/temperature limits in this Installation Guide and any applicable standard or code limitation should not be exceeded.
2. Pressure and/or the body end connection may decrease these maximum temperatures.
3. Not for use on steam service.
4. Meets API 614 Requirements (with stainless steel trim).
5. Limited to 93°C / 200°F for hot water.
6. Temperature, trim material and/or the body end connection may decrease these maximum pressures.
BODY
CATEGORY
MATERIAL
Stainless steel
SEP
Stainless steel
II
MR98 Series AD2000 Compliant
Maximum Cold Working Pressures of Body Size
and Materials
(1)(6)
See Table 2
Maximum Inlet, Outlet and Spring Case
Pressure Ratings
(1)
See Table 2
Temperature Capabilities of Body Materials
BODY MATERIAL
Stainless steel
(4)
Temperature Capabilities of Trim Materials
TRIM MATERIAL
Nitrile (NBR)
Neoprene (CR)
Fluorocarbon (FKM)
(3)
Ethylenepropylene
(EPDM)
Perfluoroelastomer
(FFKM)
Polytetrafluoroethylene
(PTFE)
Metal
Flow Coefficients
BODY SIZE
DN
In.
15
1/2
20 and 25
3/4 and 1
40 and 50
1-1/2 and 2
IEC Sizing Coefficients
BODY SIZE
DN
In.
15
1/2
20 and 25
3/4 and 1
40 and 50
1-1/2 and 2
Pressure Registration
Internal or External
Shutoff Classification Per ANSI/FCI 70-3-2004
Metal Seats: Class IV
PTFE: Class IV
Elastomer Seats: Class IV or better
(1)(2)
TEMPERATURE RANGE
-40 to 232°C / -40 to 450°F
(1)(2)
PART
TEMPERATURE RANGE
°C
-40 to 82
-40 to 180
-40 to 82
-40 to 180
-18 to 149
0 to 300
(5)
-7 to 135
20 to 275
-18 to 218
0 to 425
-40 to 204
-40 to 400
-40 to 450
-40 to 232
C
C
V
g
3.4
120
6.5
250
20.0
780
X
F
F
T
d
L
0.787
0.78
0.94
0.935
0.70
0.91
0.961
0.69
0.94
°F
(5)
C
1
35.3
38.5
39.0
K
m
0.88
0.83
0.88

Advertisement

loading

Summary of Contents for Emerson Fisher MR98 Series

  • Page 1 Maximum Inlet, Outlet and Spring Case copy of the Instruction Manual, contact your local Pressure Ratings Sales Office or view a copy at www.emerson. See Table 2 com. For further information, refer to MR98 Series Backpressure Regulators and Relief valves Instruction...
  • Page 2 MR98 Series AD2000 Compliant Table 1. MR98 Series Body Sizes and Pressure Ranges BODY SIZE CONTROL PRESSURE RANGE TYPE psig 1.0 to 2.4 15 to 35 1.7 to 5.2 25 to 75 15, 20 and 25 1/2, 3/4 and 1 4.8 to 9.7 70 to 140 9.0 to 13.8...
  • Page 3: Installation

    Emerson Process damaged or has collected foreign material during Management Regulator Technologies, shipping. For G bodies, apply pipe compound to Inc.
  • Page 4: Parts List

    MR98 Series AD2000 Compliant Startup Parts List The relief valve or backpressure regulator is factory Description set at approximately the midpoint of the spring range Body or the pressure requested, so an initial adjustment Spring Case may be required to give the desired results. With Orifice proper installation completed and relief valves properly Valve Plug...
  • Page 5 MR98 Series AD2000 Compliant SEALED ADJUSTING SCREW OPTION CONTROL LINE OPTION COMPOSITE SEAT OPTION METAL DIAPHRAGM OPTION NAMEPLATE AND FLOW ARROW GF04916 APPLY T = THREAD LOCKER L1 = GENERAL PURPOSE PTFE OR LITHIUM GREASE FOR O-RINGS L2 = ANTI - SEIZE COMPOUND L4 = GRAPHITE SEALANT FOR GRAPHITE RING 1.
  • Page 6 Technologies, Inc. All rights reserved. 04/22. McKinney, Texas 75070 USA Singapore 128461, Singapore The Emerson logo is a trademark and service mark of Emerson T +1 800 558 5853 T +65 6777 8211 Electric Co. All other marks are the property of their prospective owners.

This manual is also suitable for:

Mr98hMr98hh