4 SETTINGS AND PROCEDURES PRIOR TO OPERATION
Correct insertion
4 - 10
(c) Terminal resistor must be set (or connected) for the station of both ends on
the circuit.
Match the Q series C24 to the specifications of the external device and
connect a terminal resistor (packed with the Q series C24) according to this
section.
Connect, or set a terminal resistor at the external device according to the
instruction manual of the external device.
(The terminal resistor to connect to the Q series C24)
• When communications performed using RS-422, "330
connected.
• When communications performed using RS-485, "110
connected.
How to discriminate between the terminating resistors
330 Ω
Brown
Orange Orange
(d) When connecting the terminal resistor of the QJ71C24N-R4 to the RS-
422/485 plug-in socket block, insert the terminal resistor in the orientation
shown below.
110 Ω
Brown Brown
Brown
Inserted vertically.
MELSEC-Q
1/4 W" resistor is
1/2 W" resistor is