Feedback interface:
Offset to the start address
Channel 0
Channel 1
Byte 0: Bit 0
Byte 8: Bit 0
Byte 0: Bit 1
Byte 8: Bit 1
Byte 0: Bit 2
Byte 8: Bit 2
Byte 0: Bit 4
Byte 8: Bit 4
Byte 0: Bit 5
Byte 8: Bit 5
Byte 0: Bit 6
Byte 8: Bit 6
Byte 0: Bit 7
Byte 8: Bit 7
Byte 1: Bit 2
Byte 9: Bit 2
Byte 1: Bit 4
Byte 9: Bit 4
Byte 1: Bit 5
Byte 9: Bit 5
Byte 2: Bit 0
Byte 8: Bit 0
Byte 2: Bit 1
Byte 10: Bit 1
Technology module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
Manual, 09/2015, A5E35061186-AA
Parameter
1
ERR_PWR
ERR_24V
ERR_LD
ERR_DQA
ERR_DQB
ERR_OUT_VAL
ERR_SLOT_VAL
STS_LD_SLOT
STS_READY
STS_SW_ENABLE
STS_ENABLE
STS_DQA
Meaning
Bit 0
Indicates under voltage on the Power supply. Note that the bit is not
set if the voltage is not present.
0
PWR is not under voltage
1
PWR is detected, but under voltage
Bit 1
Indicates a short-circuit or overload on the output 24 V DC.
You must set the RES_ERROR (control interface), to reset this error.
0
No short-circuit on 24 V DC
1
Short-circuit on 24 V DC
Bit 2
Indicates an error while loading a value using the field SLOT (only in
"single-update" SLOT-mode).
0
No load error pending
1
Load error pending; you must set the RES_ERROR (control inter-
face) to reset this error and be able to SLOT again.
Bit 4
Indicates a short-circuit on the output DQn.A. You must set
RES_ERROR (control interface) to reset this error.
0
No short-circuit on DQn.A
1
Short-circuit on DQn.A
Bit 5
Indicates a short-circuit on the output DQn.B or an attempt to set
both DQn.A and DQn.B manually using SET_DQA,SET_DB, and
TM_CTRL_DQ. You must set RES_ERROR (control interface) to
reset this error.
0
No short-circuit on DQn.B
1
Short-circuit on DQn.B or attempt to set both DQn.A and DQn.B
Bit 6
Indicates that an invalid value is detected in OUTPUT_VALUE.
0
OUTPUT_VALUE is valid
1
OUTPUT_VALUE is not valid
Bit 7
Indicates that an invalid value is detected in SLOT (only in "perma-
nent-update" SLOT-mode).
0
SLOT value is valid
0 → 1
SLOT value is not valid
Bit 2
Toggle acknowledge bit for each action of the SLOT in "sin-
gle-update" SLOT-mode. Each toggle of this bit means a successful
LD_SLOT action.
Bit 4
Indicates the module is ready and parameterized.
0
Module is not parameterized
1
Module is parameterized
Bit 5
Indicates the status of SW_ENABLE (control interface).
0
SW_ENABLE cleared
1
SW_ENABLE set
Bit 0
Indicates an output sequence is running
0
Pulse output is not running
1
Pulse output is running
Bit 1
Indicates the signal level at the DQn.A digital output.
0
0 at the DQn.A digital output
1
1 at the DQn.A digital output
Modes and Functions
3.6 Frequency output mode
63