Current measurement
Current measurement is available in Pulse train mode. Your control program can use current
measurement for control and diagnostic purposes.
For more information, refer to Function: Current measurement (Page 76).
Parameters for Pulse train operating mode
Parameter
Operating mode
High-speed output
1
Function DI
Output format
Input delay
Period
Technology module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
Manual, 09/2015, A5E35061186-AA
Meaning
2 = Set the "Pulse train" operating
mode.
The output supports higher fre-
quencies (see pulse duration
range).
You can use the DIn.0 digital input
as an input or as a hardware ena-
ble. The signal at DIn.0 is interpret-
ed by the TM Pulse 2x24V, after
noise filtering by the input delay, as
the start of the output sequence.
Defines the format of the duty cycle
ratio value.
DIn.0 digital input must be stable
over the delay time (signal noise
suppression).
Period duration of the output se-
quence: You can change the period
duration in your control program
using the control interface field
SLOT.
Value range
0 = Pulse output
1 = Pulse width modulation
2 = Pulse train
3 = On/Off-delay
4 = Frequency output
5 = DC motor
0 = disabled
1 = enabled
Input
HW enable
0 = S7 analog format
1 = Per 100 (%)
2 = Per 1,000
3 = Per 10,000
0 = Off (4 μs)
1 = 0.05 ms
2 = 0.1 ms
3 = 0.4 ms
4 = 0.8 ms
5 = 1.6 ms
6 = 3.2 ms
7 = 12.8 ms
8 = 20 ms
High-speed output disabled
100 μs to 85,000,000 μs
High-speed output enabled
10 μs to 85,000,000 μs
Modes and Functions
3.4 Pulse train mode
Default
1
Disabled
Input
Per 100 (%)
0.1 ms
2,000,000 μs