Output format
Set the format and value range for ratio variables like duty cycle.
Output format options
• S7 analog output
• Per 100
• Per 1000
• Per 10000
Minimum pulse duration
Assign the minimum pulse duration that you allow in μs.
Period duration
Assign the period duration in μs.
Actual period duration
This read-only field is displayed only when isochronous mode is enabled. The period
duration value that is displayed is the actual isochronous compatible period duration that is
calculated from the value you entered in the Period duration parameter.
On-delay
Assign the On-delay in μs
Pulse timing
Pulse duration
Period duration
On-delay
Dither parameters
● Dither ramp-up time: 0 ms to 30,000 ms.
● Dither ramp-down time: 0 ms to 30,000 ms.
● Dither amplitude: 0 to 500‰
● Dither period: From (4 x PWM period) to 100,000 μs. Also, the Dither period must be
greater than 2 ms.
Current control
● Enabled
● Disabled
Technology module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
Manual, 09/2015, A5E35061186-AA
Value range
0 to 27,648
-27648 to 27648 (in DC motor mode)
0 to 100
0 to 1000
0 to 10000
Minimum
High-speed
High-speed
disabled
10 μs
1.5 μs
100 μs
10 μs
0 μs
0 μs
5.4 TIA portal Device configuration
High-speed
enabled
disabled
85,000,000 μs
Configuring
Maximum
High-speed
enabled
107