Configuring
5.4 TIA portal Device configuration
5.4.5.4

Parameter (Channel parameters)

The different operating modes restrict the configuration to a subset of these parameters and
options.
Channel parameters
High-speed output
● Enabled
– High-speed (0.1 A) option single channel output limit is 0.1 A.
– 1 channel (4 A) parallel channel connection is not possible.
– PWM mode current control is not possible.
● Disabled
– Single channel output limit is 2 A
Function DI (digital input)
● Input: DIn.0 functions as a digital input
● HW enable: DIn.0 functions as a Hardware enable for the pulse output sequence.
The HW enable option is available for these modes.
– Pulse output
– PWM ( not available for isochronous mode)
– Pulse train
– Frequency output
– DC motor (not available for isochronous mode)
● External stop (DC motor only)
See also Function: High-speed output (Page 74)
Input delay
A digital input state change must remain stable over the input delay time, before the state
change is accepted and processed. The input delay time provides noise filtering for the input
wiring.
● Off (4 μs)
● 0.05 ms
● 0.1 ms (default value)
● 0.4 ms
● 1.6 ms
● 3.2 ms
● 12.8 ms
● 20 ms