Vertical Terminations Rigid Pipe 4" X 6-5/8 - Regency CV40E-NG Owners & Installation Manual

City series zero clearance direct vent gas fireplace
Table of Contents

Advertisement

Vertical Terminations
Two 45
o
elbows equal to one 90
Vent must be supported at offsets.
Minimum distance between elbows is 1 ft. (305mm).
Maintain clearances to combustibles as listed in the "Clearances" section.
Horizontal vent must be supported every 3 feet.
Firestops are required at each loor level and whenever passing through a wall.
Must use optional rigid pipe adaptor (Part# 510-994. when using rigid pipe vent systems)
Vertical Venting with Three (3) 90
One 90
o
elbow = Two 45
Option
V
H + H1
A)
1' Min.
2' Max
B)
2' Min.
3' Max
C)
3' Min.
4' Max
D)
4' Min.
5' Max
E)
5' Min.
6' Max
F)
6' Min.
7' Max
G)
7' Min.
8' Max
Lengths do not include elbow indicated
"
Rigid Pipe 4" x 6-5/8
o
elbow. Maximum of six 45
o
Elbows
o
elbows.
V + V1
With these options,
3' Min.
max. total pipe length
4' Min.
is 30 feet with min. of
10 feet total vertical
6' Min.
and max. 8 feet total
horizontal.
7' Min.
8' Min.
Please note min. 1
foot between 90
9' Min.
elbows is required.
10' Min.
o
elbows allowed.
V1
o
H1
installation
V
H
City Series |
53