5 SETTINGS

5.3SYSTEM SETUP

a) CURRENT TERMINALS

PATH: SETTINGS
SYSTEM SETUP
 CURRENT
 TERMINAL F1
MESSAGE
This menu configures the AC current inputs. Upon power up, the B90 recognizes all the AC modules loaded in its chassis
and populates the above menu accordingly.
The current terminals are denoted in the following format: Xa, where X = {F, L, S} and a = (1, 2,..., 8}. X represents the
chassis slot containing the AC input module and a represents the AC channel of each module. For example, a B90 unit
containing the F8H and L8K modules displays the following current inputs for configuration: F1, F2, F3, F4, F5, F6, F7, F8,
L1, L2, L3, L4, L5, L6, and L7.
b) VOLTAGE TERMINALS

PATH: SETTINGS
SYSTEM SETUP
 VOLTAGE
 TERMINAL F1
MESSAGE
This menu configures the AC voltage inputs. Upon power up, the B90 recognizes all the AC modules loaded in its chassis
and populates the above menu accordingly.
The voltage terminals are denoted in the following format: Xa, where X = {F, L, S} and a = (5, 6, 7, 8}. X represents the
chassis slot containing the AC input module and a represents the AC channel of each module. For example, a B90 unit
containing the F8F and L8K modules displays the following voltage inputs: F5, F6, F7, F8, and L8.
The nominal
VT F1 SECONDARY
applied to the VT primary.
NOTE
GE Multilin

AC INPUTS

CURRENT TERMINAL F1(S8)
CT F1 PRIMARY:
65000 A
CT F1 SECONDARY:
1 A

AC INPUTS
VOLTAGE TERMINAL F1(S8)
VT F1 SECONDARY:
66.4 V
VT F1 RATIO:
1.00 :1
setting is the voltage across the relay input terminals when nominal voltage is
B90 Low Impedance Bus Differential System
5.3 SYSTEM SETUP
Range: 1 to 65000 A in steps of 1
Range: 1 A, 5 A
Range: 50.0 to 240.0 V in steps of 0.1
Range: 1.00 to 24000.00 :1 in steps of 1.00
5.3.1 AC INPUTS
5
5-69