External Faults On C-4 - GE B90 UR Series Instruction Manual

Low impedance bus differential system
Hide thumbs Also See for B90 UR Series:
Table of Contents

Advertisement

10.4 SLOPES AND HIGH SET THRESHOLD
The following table presents the results of analysis of an external fault on circuit C-4 (C-4 is connected to the North bus; C-
3 and C-5 are connected to the South bus).
By comparing the secondary currents (column 3 in the table below) with the limits of linear operation for the CTs (column 4
in the Limits of Linear Operations of the CTs table shown earlier), it is concluded that none of the CTs will saturate due to
the AC currents during this fault.
Columns 6 and 7 of the following table summarize the DC saturation threat for the fault on C-4. CT-4, CT-6, CT-7, and CT-
8 may saturate due to the DC components and may generate a spurious differential signal for both the North and South bus
relays depending on the bus configuration. The saturation will not occur before 5.85 ms and will be detected by the Satura-
tion Detector.
Table 10–7: EXTERNAL FAULT CALCULATIONS ON C-4
CT
CT-1
CT-2
CT-3
CT-4
CT-6
CT-7, CT-8
The following table presents the results of analysis of an external fault on circuit C-5 (C-5 is connected to the North bus; C-
3 and C-4 are connected to the South bus).
By comparing the secondary currents (column 3 in the table below) with the limits of linear operation for the CTs (column 4
in the Limits of Linear Operations of the CTs table shown earlier), it is concluded that none of the CTs will saturate due to
the AC currents during this fault.
Columns 6 and 7 of the following table summarize the DC saturation threat for the fault on C-5. CT-4, CT-5, CT-7, and CT-
8 may saturate due to the DC components and may generate a spurious differential signal for both the North and South bus
relays depending on the bus configuration. The saturation will not occur before 4.83 ms and will be detected by the Satura-
tion Detector.
Table 10–8: EXTERNAL FAULT CALCULATIONS ON C-5
CT
CT-1
CT-2
CT-3
CT-4
CT-5
CT-7, CT-8
10
10-8
I
(KA)
I
(A SEC)
FAULT
FAULT
0
0.00
0
0.00
6.0
25.00
9.0
45.00
3.0
15.00
9.0
37.50
I
(KA)
I
(A SEC)
FAULT
FAULT
0
0.00
0
0.00
6.0
25.00
5.0
25.00
11.0
55.00
11.0
45.83
B90 Low Impedance Bus Differential System
T
(MS)
AC
DC
SATURATION
N/A
No
N/A
No
5
No
40
No
40
No
40
No
T
(MS)
AC
DC
SATURATION
N/A
No
N/A
No
5
No
30
No
30
No
30
No
10 APPLICATION OF SETTINGS

10.4.5 EXTERNAL FAULTS ON C-4

DC
T
(MS)
SAT
SATURATION
No
N/A
No
N/A
No
N/A
Yes
5.85
Yes
35.25
Yes
9.40
10.4.6 EXTERNAL FAULTS ON C-5
DC
T
(MS)
SAT
SATURATION
No
N/A
No
N/A
No
N/A
Yes
15.19
Yes
4.83
Yes
7.16
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents