GE B90 UR Series Instruction Manual page 345

Low impedance bus differential system
Hide thumbs Also See for B90 UR Series:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 22 of 48)
ADDR
REGISTER NAME
Instantaneous Overcurrent (Read/Write Grouped Setting) (24 modules)
7600
Instantaneous Overcurrent 1 Function
7601
Instantaneous Overcurrent 1 CT
7602
Instantaneous Overcurrent 1 Pickup
7603
Instantaneous Overcurrent 1 Pickup Delay
7604
Instantaneous Overcurrent 1 Reset Delay
7605
Instantaneous Overcurrent 1 Block
7607
Instantaneous Overcurrent 1 Target
7608
Instantaneous Overcurrent 1 Events
7609
Reserved (2 items)
760A
...Repeated for Instantaneous Overcurrent 2
760B
...Repeated for Instantaneous Overcurrent 3
760C
...Repeated for Instantaneous Overcurrent 4
760E
...Repeated for Instantaneous Overcurrent 5
760F
...Repeated for Instantaneous Overcurrent 6
7612
...Repeated for Instantaneous Overcurrent 7
7614
...Repeated for Instantaneous Overcurrent 8
7615
...Repeated for Instantaneous Overcurrent 9
7618
...Repeated for Instantaneous Overcurrent 10
7619
...Repeated for Instantaneous Overcurrent 11
761C
...Repeated for Instantaneous Overcurrent 12
761E
...Repeated for Instantaneous Overcurrent 13
761F
...Repeated for Instantaneous Overcurrent 14
7622
...Repeated for Instantaneous Overcurrent 15
7623
...Repeated for Instantaneous Overcurrent 16
7626
...Repeated for Instantaneous Overcurrent 17
7628
...Repeated for Instantaneous Overcurrent 18
7629
...Repeated for Instantaneous Overcurrent 19
762C
...Repeated for Instantaneous Overcurrent 20
762F
...Repeated for Instantaneous Overcurrent 21
7631
...Repeated for Instantaneous Overcurrent 22
7632
...Repeated for Instantaneous Overcurrent 23
7633
...Repeated for Instantaneous Overcurrent 24
Time Overcurrent (Read/Write Grouped Setting) (24 modules)
7700
Time Overcurrent 1 Function
7701
Time Overcurrent 1 CT Setting
7702
Time Overcurrent 1 Pickup
7703
Time Overcurrent 1 Curve
7704
Time Overcurrent 1 Multiplier
7705
Time Overcurrent 1 Reset
7706
Time Overcurrent 1 Block
7708
Time Overcurrent 1 Target
7709
Time Overcurrent 1 Events
770A
Reserved (3 items)
770C
...Repeated for Time Overcurrent 2
770D
...Repeated for Time Overcurrent 3
7710
...Repeated for Time Overcurrent 4
7712
...Repeated for Time Overcurrent 5
7714
...Repeated for Time Overcurrent 6
7716
...Repeated for Time Overcurrent 7
7718
...Repeated for Time Overcurrent 8
771A
...Repeated for Time Overcurrent 9
771B
...Repeated for Time Overcurrent 10
771D
...Repeated for Time Overcurrent 11
GE Multilin
RANGE
0 to 1
0 to 23
0.001 to 30
0 to 65.535
0 to 65.535
0 to 4294967295
0 to 2
0 to 1
0 to 65535
0 to 1
0 to 23
0.001 to 30
0 to 16
0 to 600
0 to 1
0 to 4294967295
0 to 2
0 to 1
0 to 65535
B90 Low Impedance Bus Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F102
---
1
F400
pu
0.001
F001
s
0.001
F001
s
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F400
pu
0.001
F001
---
1
F103
0 (IEEE Mod Inv)
---
0.01
F001
---
1
F104
0 (Instantaneous)
---
1
F300
---
1
F109
---
1
F102
---
1
F001
DEFAULT
0 (Disabled)
0
1200
0
0
0
0 (Self-reset)
0 (Disabled)
0
B
0 (Disabled)
0
1200
100
0
0 (Self-reset)
0 (Disabled)
0
B-29

Advertisement

Table of Contents
loading

Table of Contents