Non-Volatile Latches - GE B90 UR Series Instruction Manual

Low impedance bus differential system
Hide thumbs Also See for B90 UR Series:
Table of Contents

Advertisement

5.4 FLEXLOGIC
TIMER 1 DROPOUT DELAY: Sets the time delay to dropout. If a dropout delay is not required, set this function to "0".

PATH: SETTINGS
FLEXLOGIC
 LATCH 1
The non-volatile latches provide a permanent logical flag that is stored safely and will not reset upon reboot after the relay
is powered down. Typical applications include sustaining operator commands or permanently block relay functions, such as
Autorecloser, until a deliberate interface action resets the latch. The settings element operation is described below:
5
LATCH 1 TYPE: This setting characterizes Latch 1 to be Set- or Reset-dominant.
LATCH 1 SET: If asserted, the specified FlexLogic operands 'sets' Latch 1.
LATCH 1 RESET: If asserted, the specified FlexLogic operand 'resets' Latch 1.
LATCH N
LATCH N
LATCH N
TYPE
SET
RESET
Reset
ON
Dominant
OFF
ON
OFF
Set
ON
Dominant
ON
OFF
OFF
Figure 5–41: NON-VOLATILE LATCH OPERATION TABLE (N = 1 to 16) AND LOGIC
5-92


NON-VOLATILE LATCHES

LATCH 1
FUNCTION: Disabled
LATCH 1 TYPE:
MESSAGE
Reset Dominant
LATCH 1 SET:
MESSAGE
Off
LATCH 1 RESET:
MESSAGE
Off
LATCH 1
MESSAGE
TARGET: Self-reset
LATCH 1
MESSAGE
EVENTS: Disabled
LATCH N
LATCH N
ON
OFF
OFF
ON
OFF
OFF
Previous
Previous
State
State
ON
OFF
ON
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
OFF
Previous
Previous
State
State
ON
OFF
ON
B90 Low Impedance Bus Differential System
5.4.7 NON-VOLATILE LATCHES
LATCH 1(16)
Range: Disabled, Enabled
Range: Reset Dominant, Set Dominant
Range: FlexLogic operand
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
SETTING
SETTING
LATCH 1 FUNCTION:
LATCH 1 TYPE:
Disabled=0
Enabled=1
RUN
SETTING
LATCH 1 SET:
Off=0
SET
SETTING
LATCH 1 SET:
Off=0
RESET
5 SETTINGS
FLEXLOGIC OPERANDS
LATCH 1 ON
LATCH 1 OFF
842005A1.CDR
GE Multilin