Notification Appliance Circuit Power Configurations
The total current drawn from a Notification Appliance Circuit cannot exceed 3.0 amps
(subject to the limitations of the power supply). Figure 6-6 illustrates some of the
typical power supply/Notification Appliance Circuit configurations possible.
Figure 6-6: Typical Supply/Notification Circuit Configurations
MPS
MPS
MPS
MPS
AVPS-24F
J5
CPU
Module
J5
CPU
Module
J6
J5
IC-4F
J6
J5
CPU
Module
J6
J5
IC-4F
J6
J5
ICE-
4F
J5
CPU
Module
J5
IC-4F
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
IC-4F
ICE-4F
Bottom view of the
IC-4F/ICE-4F
These two Notification
Appliance Circuits share 2.0
amps.
These six
Notification Appliance
Circuits share 2.0 amps.
These ten
Notification Appliance
Circuits share 2.0 amps.
These two Notification Ap-
pliance Circuits share 2.0
amps.
These four Notification Ap-
pliance Circuits share the
total 3.0 amps of current on
the AVPS-24F.
41