X482: Analog Inputs/Outputs; Table 3-8 Terminal Block X482; Table 3-9 Technical Specifications - Siemens SINAMICS S120 Equipment Manual

Control units and additional system components
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

3.2.3.5

X482: Analog inputs/outputs

Table 3-8
Terminal block X482
Terminal
1
2
3
4
5
6
7
8
Max. connectable cross-section: 0.5 mm
Type: Spring-loaded terminal 1 (see Appendix A)
1) AI: analog input, AO: analog output
Note
An open input is interpreted as approximately "0V".
The power supply of the analog inputs/outputs is drawn via the option slot of the Control Unit
and not via X424.
The shield is connected to the Control Unit (see Electrical connection).
Caution
The common-mode range must not be infringed.
The analog differential voltage signals can have a maximum offset voltage of +/-30 V with
respect to the ground potential. If the range is infringed, incorrect results may occur during
analog/digital conversion.
Handling analog inputs
The following reference contains more information about analog inputs:
Reference: /IH1/ SINAMICS S120 Commissioning Manual
Equipment Manual Control Units and Additional System Components
Equipment Manual, (GH1), 12/2004 Edition, 6SL3097-2AH00-0BP1
Name
1)
AI 0+
AI 0-
AI 1+
AI 1-
AO 0+
AO 0-
AO 1+
AO 1-
2
Additional System Components
3.2 Option Board: Terminal Board 30 (TB30)
Technical specifications
Voltage: -10 V to +10 V
Internal resistance: 65 kΩ
Resolution: 13 bits + sign
Voltage range: -10 V to +10 V
Load current: max. -3 mA to +3 mA
Resolution: 11 bits + sign
Continued-short-circuit-proof
3-11