Configuring Environmental Monitoring (EMCU) Thresholds
If an EMCU is connected to the PRO2 unit, the Sensors page will also allow configuration of water, contact closure
and analog-to-digital (ADC) voltage sensors – to provide sensor name and SNMP/Email notifications.
In addition, for ADC voltage sensors only, high/low warning/alarm thresholds can be set. Water and contact closure
sensors can have either Normal or Alarm status – there are no other states or value ranges.
To set ADC voltage sensor thresholds:
1. Click the ADC sensor thresholds link at the bottom of the Sensors page to display the configuration page:
2. Provide the threshold hysteresis between event state and recovery. Range is 0-20; default is 1.
3. Set the low/high alarm and low/high warning threshold values for the ADC sensor. Range is 0-255;
default is 0.
4. Click Apply.
Using the Web Interface
Switched PRO2 – User Guide
81