show sensors
Shows sensor configuration values.
Command Syntax
show sensors
Command Access
Admin level only
Example
Switched CDU: show sensors
Using the Command Line Interface (CLI)
Sensor
ID
Sensor Name
------
--
-----------
Temp
A1
Temp_Sensor_A1
Temp
A2
Temp_Sensor_A2
Temp
C1
Temp_Sensor_C1
Temp
C2
Temp_Sensor_C2
Humid
A1
Humid_Sensor_A1
Humid
A2
Humid_Sensor_A2
Humid
C1
Humid_Sensor_C1
Humid
C2
Humid_Sensor_C2
Contact C1
Contact_Sensor_C1
Contact C2
Contact_Sensor_C2
Contact C3
Contact_Sensor_C3
Contact C4
Contact_Sensor_C4
Water
C1
Water_Sensor_C1
ADC
C1
ADC_Sensor_C1
SNMP
Sensor
ID
Notif.
------
--
------
Temp
A1
enabled
Temp
A2
enabled
Temp
C1
enabled
Temp
C2
enabled
Humid
A1
enabled
Humid
A2
enabled
Humid
C1
enabled
Humid
C2
enabled
Contact C1
enabled
Contact C2
enabled
Contact C3
enabled
Contact C4
enabled
Water
C1
enabled
ADC
C1
disabled
Common Sensor Settings
Temperature Scale:
Temperature Sensor Hysteresis:
Humidity Sensor Hysteresis:
ADC Sensor Hysteresis:
Switched PRO2 – User Guide
Email
Notif.
Lo-Alrm
Lo-Warn
------
-------
-------
enabled
1C
5C
enabled
1C
5C
enabled
1C
5C
enabled
1C
5C
enabled
5% RH
10% RH
enabled
5% RH
10% RH
enabled
5% RH
10% RH
enabled
5% RH
10% RH
enabled
--
--
enabled
--
--
enabled
--
--
enabled
--
--
enabled
--
--
disabled
0
0
Celsius
1C
2% RH
1
Hi-Warn
Hi-Alrm
-------
-------
45C
50C
45C
50C
45C
50C
45C
50C
90% RH
95% RH
90% RH
95% RH
90% RH
95% RH
90% RH
95% RH
--
--
--
--
--
--
--
--
--
--
255
255